Experiment No: 15
Determination of Splitting Tensile Strength of Cylindrical Concrete Specimens
Introduction
The
splitting tension test, a method used to determine the tensile strength of
concrete, originated during World War II in Rio de Janeiro. The city's rapid
expansion led to the relocation of the small church of Sá´o Pedro, which was
occupied by a section of the redesigned roadway system. Due to the shortage of
steel rollers, concrete cylinders covered by 9mm thick steel plates were used
as rollers to transport the church. Engineer Lobo Carneiro noticed uniform and
consistent splitting failure in the cylinders, which led him to study Hertz's
work on stress distribution for concentrated loads applied to cylinders.
Carneiro concluded that this configuration was suitable for measuring the
indirect tensile strength of concrete. However, plans for the church's relocation
were abandoned due to weak masonry and potential collapse risks during
transport. The splitting test, now known as the "Brazilian test" in
rock mechanics, became popular for measuring the tensile strength of brittle
materials.
This test involves applying a diametral compressive force to a cylindrical concrete specimen until failure occurs. This results in tensile stresses on the load-containing plane and high compressive stresses in the area around it. Tensile failure occurs due to triaxial compression, allowing the areas to withstand higher compressive stresses than a uniaxial compressive strength test. Thin plywood bearing strips distribute the load along the cylinder's length. The maximum load sustained is divided by geometrical factors to obtain splitting tensile strength.
Scope
This
lab report covers the procedures outlined in ASTM C496 for determining the
splitting tensile strength of cylindrical concrete specimens. This method is
widely used in structural engineering to assess the tensile properties of
concrete, which are important for design purposes.
Purpose
To determine the Splitting
Tensile Strength of Cylindrical Concrete Specimens.
ASTM Designation
ASTM C496—Splitting Tensile Strength of Cylindrical Concrete Specimens.
Terminology
Concrete —
a composite material that consists
essentially of a binding medium within which are embedded particles or
fragments of aggregate; in hydraulic-cement concrete, the binder is formed from
a mixture of hydraulic cement and water.
concrete, fresh —
concrete that possesses enough of its
original workability so that it can be placed and consolidated by the intended
methods.
concrete, hardened —
concrete that has developed
sufficient strength to serve some defined purpose or resist a stipulated
loading without failure.
Consistency (fresh cementitious mixture)—
the relative mobility or ability to flow.
Curing —
action taken to maintain moisture and
temperature conditions in a freshly-placed cementitious mixture to allow
hydraulic cement hydration and (if applicable) pozzolanic reactions to occur so
that the potential properties of the mixture may develop.
Pozzolan —
a siliceous or siliceous and
aluminous material, which in itself possesses little or no cementitious value
but will, in finely divided form and in the presence of moisture, chemically
react with calcium hydroxide at ordinary temperatures to form compounds
possessing cementitious properties.
Cementitious Material (Hydraulic) —
an inorganic material or a mixture of
inorganic materials that sets and develops strength by chemical reaction with
water by formation of hydrates and is capable of doing so under water.
Fracture —
The failure of the specimen under compression load.
Splitting Tensile Strength —
The tensile strength of concrete
determined by applying compressive forces along its length until failure
occurs, indirectly inducing tension.
Significance and Use
Splitting tensile strength is
typically larger than direct tensile strength and lower than flexural strength
(modulus of rupture). Splitting tensile strength is utilized in the design of
structural lightweight concrete elements to evaluate the shear resistance
supplied by concrete and to calculate the development length of reinforcement.
Apparatus
Testing
Machine:
The testing machine shall be of a
type having sufficient capacity and capable of providing the required rates of loading.
Supplementary
bearing bar or plate:
If the diameter or the largest dimension
of the upper bearing face or the lower bearing block is less than the length of
the cylinder to be tested, a supplementary bearing bar or plate of machined
steel shall be used. The surfaces of the bar or plate shall be machined to
within 6 0.001 in. [0.025 mm] of planeness, as measured on any line of contact
of the bearing area. It shall have a width of at least 2 in. [50 mm], and a
thickness not less than the distance from the edge of the spherical or
rectangular bearing block to the end of the cylinder. The bar or plate shall be
used in such manner that the load will be applied over the entire length of the
specimen.
Bearing Strips:
Two bearing strips of nominal 1⁄8
in. [3.2 mm] thick plywood, free of imperfections, approximately 1 in. [25 mm] wide,
and of a length equal to, or slightly longer than, that of the specimen shall
be provided for each specimen. The bearing strips shall be placed between the
specimen and both the upper and lower bearing blocks of the testing machine or
between the specimen and supplemental bars or plates, when used. Bearing strips
shall not be reused.
Specimens:
·
The
test specimens shall conform to the size, molding, and curing requirements of ASTM
C 31
·
Moist-cured
specimens, during the period between their removal from the curing environment
and testing, shall be kept moist by a wet burlap or blanket covering, and shall
be tested in a moist condition as soon as practicable.
·
The
following curing procedure shall be used for evaluations of light-weight
concrete: specimens tested at 28 days shall be in an air-dry condition after 7
days moist curing followed by 21 days drying at 23.0 ± 2.0°C and 50 6 5 %
relative humidity.
Procedure
Marking:
Draw
diametrical lines on each end of the specimen using a suitable device that will
ensure that they are in the same axial plane or as an alternative, use the
aligning jig.
Measurements:
[1] Determine the diameter of the test specimen to the nearest 0.25 mm
(0.01in.) by averaging three diameters measured near the ends and the middle of
the specimen and lying in the plane containing the lines marked on the two ends.
[2]
Determine the length of the
specimen to the nearest 2.5 mm (0.1 in.) by averaging at least two length
measurements taken in the plane containing the lines marked on the two ends.
Positioning
Using Marked Diametral Lines:
Center one of the plywood strips
along the center of the lower bearing block. Place the specimen on the plywood
strip and align so that the lines marked on the ends of the specimen are
vertical and centered over the plywood strip. Place a second plywood strip
lengthwise on the cylinder, centered on the lines marked on the ends of the
cylinder. Position the assembly to ensure the following conditions:
·
The
projection of the plane of the two lines marked on the ends of the specimen
intersects the center of the upper bearing plate, and
·
The
supplementary bearing bar or plate, when used, and the center of the specimen
are directly beneath the center of thrust of the spherical bearing block
Positioning
by Use of Aligning Jig:
Position the bearing strips, test cylinder, and supplementary
bearing bar by means of the aligning jig, and center the jig so that the
supplementary bearing bar and the center of the specimen are directly beneath
the center of thrust of the spherical bearing block.
Figure: Schematic Diagram of Cylinder Splitting
Test
Rate of Loading:
Apply
the load continuously and without shock, at a constant rate within the range
100 to 200 psi/min [0.7 to 1.4 MPa/min] splitting tensile stress until failure
of the specimen. Record the maximum applied load indicated by the testing
machine at failure. Note the type of failure and the appearance of the
concrete.
The relationship between splitting
tensile stress and applied load is shown in formula. The required loading range
in splitting tensile stress corresponds to applied total load in the range of
11 300 to 22 600 lbf [50 to 100 kN]/min for 6 by 12-in. [150 by 300-mm]
cylinders.
Calculation
Calculate the splitting tensile
strength of the specimen as follows:
T = 2P/pld
where:
T = splitting tensile strength, psi [MPa],
P = maximum applied load indicated by the testing machine, lbf
[N],
l = length, in. [mm], and
d = diameter, in. [mm].
Report:
·
Identification
number,
·
Diameter
and length, in. [mm],
·
Maximum
load, lb. [N],
·
Splitting
tensile strength calculated to the nearest 5 psi [0.05 MPa],
·
Estimated
proportion of coarse aggregate fractured during test,
·
Age
of specimen,
·
Curing
history,
·
Defects
in specimen,
·
Type
of fracture, and
·
Type
of specimen
Lab
Questions:
Basic
Understanding
1. What is splitting
tensile strength, and why is it important for concrete?
2. How does the
splitting tensile strength differ from the compressive strength of concrete?
3. Why is the tensile
strength of concrete tested indirectly through the splitting method?
Procedure
and Equipment
4. Can you describe the
procedure for determining the splitting tensile strength of concrete using
cylindrical specimens?
5. What is the
significance of the loading strip used in the splitting tensile strength test?
6. Why are cylindrical
specimens placed horizontally between the loading surfaces during the test?
7. How is the load
applied in this test, and why is it important to apply it gradually?
8. What type of machine
is used for the splitting tensile strength test?
9. What are the
dimensions of the cylindrical specimens used in this test?
10. Why is it important
to cure the concrete cylinders before testing their tensile strength?
Calculation
and Interpretation
11. How do you calculate
the splitting tensile strength from the test data?
12. What factors can
influence the splitting tensile strength of concrete?
13. How do the dimensions
of the specimen affect the tensile strength calculation?
14. What would you infer
if the specimen fails prematurely or shows unusually low tensile strength?
15. How does the
water-cement ratio affect the splitting tensile strength of concrete?
16. What is the
significance of the failure pattern observed in the concrete specimen after
testing?
Standards
and Specifications
17. Which standards
(e.g., ASTM, IS) are followed for determining the splitting tensile strength of
concrete?
18. What are the typical
values of splitting tensile strength for normal-strength concrete?
19. How does the curing
duration affect the splitting tensile strength?
20. What are the
acceptable tolerances for splitting tensile strength in various construction
applications?
Application
and Practical Considerations
21. How does the
splitting tensile strength of concrete relate to its performance in structures
under tension?
22. What are the
practical implications of having a low splitting tensile strength in concrete?
23. What are the possible
reasons for an unexpectedly low or high splitting tensile strength result?
24. How can the splitting
tensile strength of concrete be improved?
25. What role does
aggregate size and type play in the tensile strength of concrete?
26. How do admixtures
affect the splitting tensile strength of concrete?