Classification of Buildings

PART III

Chapter 2: Classification of Buildings Based on Occupancy

2.1 Occupancy Classification

2.1.1Every building or portion thereof and land-use shall be classified according to its use or the character of its occupancy as a building of Occupancy A, B, C, D, E, F, G, H, I, J, K, L or M as defined below:

Occupancy A: Residential

Occupancy B: Educational

Occupancy C: Institution for care

Occupancy D: Health Care

Occupancy E: Business

Occupancy F: Mercantile

Occupancy G: Industrial

Occupancy H: Storage

Occupancy I: Assembly

Occupancy J: Hazardous

Occupancy K: Garages

Occupancy L: Utilities

Occupancy M: Miscellaneous

2.1.2Utilities under Occupancy L is incidental to operation in all other type of occupancy except Occupancy J shall be considered as non-separated use of the main occupancy but shall be taken special safety measure as per provision of this Code.

2.1.3Any occupancy or use type not mentioned specifically in Table 3.2.6 (A-Z list) or elsewhere in this Code shall be classified by the Board of Appeals under the occupancy group to which its use most closely resembles, considering the life safety and fire hazard.

2.1.4Each occupancy group shall be subdivided as detailed in the following sections. The detail classification including mixed occupancy provided in the Table 3.2.6 (A-Z list) is non-exhaustive. If there is any use or character of occupancy in a building which is not mentioned here, it shall be classified as per provision of Sec 2.1.3 of this Chapter.

2.1.5 Occupancy A: Residential Buildings

This occupancy type shall include any building or portion thereof providing sleeping and living accommodations to related or unrelated groups of people, with or without independent bathroom, cooking or dining facilities, except any building classified under Occupancy C or D. This Occupancy shall be subdivided as follows:

2.1.5.1 Single Family Dwelling (A1)

These shall include any building, row type or semi-detached or detached from neighboring buildings by distances required by this Code and having independent access to the plot, which is used as private dwelling by members of a single family.

2.1.5.2 Two Family Dwelling (A2)

These shall include any building, row type or semi-detached or detached from neighboring buildings by distances required by this Code and having shared or independent access for two families and having facilities for living, cooking and bathroom facilities independent of each other.

2.1.5.3 Flats or Apartments (A3)

These shall include any building or portion thereof which is provided for more than two families, having facilities for living, cooking and bathroom facilities independent of each other.

2.1.5.4 Mess, Boarding Houses, Dormitories and Hostels (A4)

These shall include any building or portion thereof in which sleeping, living accommodations and bathroom are provided for groups of related or unrelated persons, with or without common dining and facilities, and with common cooking under single management control or with individual or group cooking facilities.

2.1.5.5 Hotels and Lodging Houses (A5)

These shall include any building, a portion thereof or group of buildings under single management, in which sleeping, living accommodation and bathroom facilities are provided with or without dining facilities but without cooking facilities for adult individuals, is provided for hire on transient or permanent basis.

2.1.6 Occupancy B: Educational Facilities

This occupancy type shall include any building or portion thereof in which education, training and care are provided to children or adults. This Occupancy shall be subdivided as follows:

2.1.6.1 Educational Facilities up to Higher Secondary Level (B1)

These shall include any building or portion thereof used for purposes involving assembly for instruction, education and recreation of more than six persons on regular basis to fulfil the requirement of an academic curriculum approved by the Government up to Higher Secondary (12th Grade), and which is not covered by occupancy I.

2.1.6.2 Facilities for Training and for Above-Secondary Level (B2)

These shall include any building or portion thereof used for purposes involving assembly for instruction, education, training and recreation of more than six persons, and which is not covered by occupancy I and B1.

2.1.6.3 Pre-School Facilities (B3)

These shall include any building or portion thereof used for purposes involving care, recreation and education of children more than six in number, who have not yet reached the age to attend the school.

2.1.7 Occupancy C: Institution for Care

Buildings classified under this occupancy shall include those used for purposes of institutional care of the occupants, such as detention for correctional or penal purposes, medical or nursing care of persons suffering from illness or infirmity due to mental condition, or accommodation of children or minor, where the personal liberty of the inmate is restricted. These buildings shall ordinarily provide accommodation for sleeping, dining and other provisions approved by the authority for the occupants. This occupancy shall be subdivided as follows:

2.1.7.1 Institution for Care of Children (C1)

These shall include any building or portion thereof or group of buildings under single management used as an institution for the full time care of children or minor, each providing accommodation for sleeping, dining and other provisions approved by the authority for more than six children.

2.1.7.2 Custodial Institution for Physically Capable Adults (C2)

These shall include any building or portion thereof or group of buildings under single management used for purposes of full time care and custody of adult or mentally disabled persons but physically capable of responding to emergency.

2.1.7.3 Custodial Institution for the Incapable Adults (C3)

These shall include any building or portion thereof or group of buildings under single management used for purposes of full time care and custody of persons physically or mentally incapable of responding to emergency.

2.1.7.4 Penal and Mental Institution for Children (C4)

These shall include any building or portion thereof or group of buildings under single management used for housing children under restraint, or who are detained for penal and corrective purposes, in which personal liberty of the inmates is restricted.

2.1.7.5 Penal and Mental Institution for Adults (C5)

These shall include any building or portion thereof or group of buildings under single management used for housing persons under restraint, or who are detained for penal and corrective purposes, in which personal liberty of the inmates is restricted.

2.1.8 Occupancy D: Health Care Facilities

Buildings under this Occupancy group shall include those used for purposes of providing medical care, diagnostic facilities and treatment to persons suffering from physical discomfort, in which sleeping accommodation may or may not be provided. This Occupancy shall be subdivided as follows:

2.1.8.1 Normal Medical Facilities (D1)

These shall include any building or portion thereof or group of buildings under single management in which essential medical facilities having surgery, emergency and casualty treatment facilities, general or specialized medical and other treatment are provided to persons suffering from physical discomfort.

2.1.8.2 Emergency Medical Facilities (D2)

These shall include any building or portion thereof used for purposes of providing essential medical facilities having surgery, emergency, casualty treatment facilities, general or specialized medical and other treatment is provided to persons suffering from physical discomfort. This Type shall be equipped and designated to handle post disaster emergency, by construction it is required to remain operational during and after disasters, built as a part of disaster preparedness program.

2.1.9 Occupancy E: Business

These shall include any building or portion thereof which is used for any business transaction other than mercantile. This Occupancy shall be subdivided as follows:

2.1.9.1 Office (E1)

These shall include any building or part thereof which is used for paper works, documentations, only display of samples of Products but not for direct sale, maintaining accounts and records for administrative or consulting services, banking or activities for business purposes and professional training.

2.1.9.2 Research and Testing Laboratories (E2)

These shall include any building or portion thereof which is used as research establishment and/or test laboratory involving hazardous materials within the limit of exempted quantity permitted in this Code.

2.1.9.3 Essential Services (E3)

These shall include any building or portion thereof used for purposes of providing emergency services and utilities which are required to remain operational during and after a disaster or other emergency situations.

2.1.10 Occupancy F: Mercantile

This occupancy type shall include any building or portion thereof or group of buildings which is used for display and sale of merchandises. This Occupancy shall be subdivided as follows:

2.1.10.1 Small Shops and Market (F1)

These shall include any building or portion thereof with an area divided or undivided not exceeding 300 m², used for purposes of display and sale of merchandise, either wholesale or retail, with or without incidental storage and service facilities.

2.1.10.2 Large Shops and Market (F2)

These shall include any building or portion thereof with an area divided or undivided more than 300 m² used for purposes of display and sale of merchandise, either wholesale or retail, with or without incidental storage and service facilities.

2.1.10.3 Refueling Station (F3)

These shall include any building or portion thereof used for providing refueling and maintenance without repair services for automobiles which is moderately hazardous in nature.

2.1.11 Occupancy G: Industrial Buildings

Buildings under this Occupancy shall be subdivided on the basis of hazard potential of the contents and the processes of the industry. The hazard shall generally mean the relative danger of the start of fire and the rapidity of its spread, the danger of smoke and gases generated that pose a potential threat to the safety of the occupants of the building. Unless areas with different degrees of hazard are effectively segregated and separated in accordance with the provisions of this Code, the most hazardous area in a building shall govern its classification. This occupancy shall also include facilities for public utility services at the producer or distributor’s end that deals with generation and distribution of utility facilities. Any such building or portion thereof, which is not using hazardous material quantified and categorized in occupancy group J, shall be subdivided as follows:

2.1.11.1 Low Hazard Industry (G1)

These shall include any industrial building in which the contents are of such low combustibility and the processes conducted therein are of such low hazardous nature that danger of self-ignition and self-propagation of fire is nonexistent, the only danger being an onset of fire from external sources with the resulting danger to life and property.

2.1.11.2 Moderate Hazard Industry (G2)

These shall include any industrial building in which the contents are moderately combustible and the industrial processes conducted therein are liable to give rise to a fire which will spread with moderate rapidity, giving off considerable smoke.

2.1.12 Occupancy H: Storage Buildings

Buildings under this Occupancy group shall include any building or portion thereof used primarily for storage or sheltering of goods, wares, merchandises, vehicles or animals. Any such building or portion thereof, which is not used for storing hazardous material quantified and categorized in occupancy group J, shall be subdivided as follows:

2.1.12.1 Low Fire-risk Storage (H1)

These shall include any building or portion thereof which is used for storage of materials or other contents which do not constitute the danger of self-ignition, and in the event of fire the rate of burning shall be less than moderate rapidity.

2.1.12.2 Moderate Fire-risk Storage (H2)

These shall include any building or portion thereof which is used for storage of materials which do not constitute the danger of self-ignition but which in the event of fire will burn with moderate rapidity.

Items which shall be deemed to render a building hazardous are specified in Sec 2.14.3 along with the exempted amount for each item.

2.1.13 Occupancy I: Assembly

Buildings under this Occupancy group shall include any building or portion thereof in which groups of people congregate or assemble for recreation, amusement, social, religious, political, cultural, travel and similar purposes. This Occupancy shall be subdivided as follows:

2.1.13.1 Large Assembly with Fixed Seats (I1)

This occupancy shall include a building or a portion thereof for assembly in a space provided with fixed seats for 1000 or more persons. Assembly buildings under this subdivision may be for theatrical, operatic performances or cinema projection having or not a raised stage, proscenium curtains, scenery loft or projection screen, lighting equipment, projection booth and necessary theatrical and mechanical equipment.

2.1.13.2 Small Assembly with Fixed Seats (I2)

This occupancy type shall include any building or portion thereof primarily meant for use as described for buildings under Occupancy I1, but with fixed seats for less than 1000 persons in a space. These assembly buildings may or may not be provided with a legitimate theatrical stage or related accessories or equipment.

2.1.13.3 Large Assembly without Fixed Seats (I3)

This occupancy type shall include any building or portion thereof for assembly in a space, in which there are no fixed seats, which may or may not be provided with a legitimate stage or theatrical accessories, and which has accommodation for 300 or more persons.

2.1.13.4 Small Assembly without Fixed Seats (I4)

This occupancy type shall include any building or portion thereof primarily intended for use as described in Occupancy I3, but with accommodation for less than 300 persons in a space.

2.1.13.5 Sports Facilities (I5)

This occupancy type shall include any building or portion thereof meant for assembly of spectators for recreational and amusement purpose mainly related to sports.

2.1.14 Occupancy J: Hazardous Buildings

Any Building or portion thereof used as storage, industrial, research and other facilities dealing with hazardous material in excess of exempted quantity defined in the Table 3.2.5 or any micro-biological facilities shall be categorized in this Occupancy group.

Definition of hazard and the amount of such materials which shall be deemed to render a building hazardous are set forth in Sec 2.14.3. This Occupancy shall be subdivided as follows:

2.1.14.1 Explosion Hazard Buildings (J1)

These shall include any building or portion thereof which is used for storage, handling, processing or manufacture of explosive materials and products that have explosion hazard.

2.1.14.2 Chemical Hazard Buildings (J2)

These shall include any building or portion thereof which is used for storage, handling, processing or manufacture of materials and products that are highly corrosive, toxic, poisonous and physically harmful including corrosive and toxic alkalis, acid or other liquids or chemicals, producing flame, fumes, radiation, and explosive, poisonous, irritant and corrosive gases.

2.1.14.3 Biological Hazard Buildings (J3)

These shall include any building or portion thereof which is used for storage, handling, processing or manufacture of materials and products that use biological processes and in which the risk of harmful biological threat to the occupants exist.

2.1.14.4 Radiation Hazard Buildings (J4)

These shall include any building or portion thereof which is used for storage, handling, processing or manufacture of materials and products that use nuclear and radioactive processes and in which the risk of radioactive contamination exists.

2.1.15 Occupancy K: Garage

These occupancy types shall include any building or portion thereof used one or more vehicles having containers of flammable liquid or compressed gas or carrying power or combination of any of these as a supply source for self-propelling are kept for use, sale, rental purpose, storage, repair, exhibition and all those floors of a building or portion thereof in which such vehicles are not separated by suitable cutoff to prevent fire spreading.

2.1.15.1 Parking Garage (K1)

This occupancy type shall include any building or portion thereof used solely for parking Motor Vehicles for a limited period of time.

2.1.15.2 Private Garage (K2)

This occupancy type shall include any building or portion thereof used as store of owner's or tenant's Motor Vehicles for private use for unlimited period of time.

2.1.15.3 Repair Garage and Showrooms (K3)

This occupancy type shall include any building or portion thereof wherein repair of electrical or mechanical system or denting or painting works of body is performed on any type of vehicles and includes associated floor spaces used as office, showrooms, incidental store and parking.

2.1.16 Occupancy L: Utility

This occupancy type shall include any building or portion thereof used to install any type of equipment to provide support service to any building or portion thereof or group of buildings of all occupancy groups and with special provisions for occupancy J.

This shall also include all public and private utility facilities of the consumer’s end that are located within the consumer’s site and all installations are required special care to ensure life and property safety as per provisions of this Code.

2.1.17 Occupancy M: Miscellaneous

Buildings under this Occupancy group shall include special buildings not covered in other Occupancy groups. These Occupancies shall be subdivided as follows:

2.1.17.1 Special Structure (M1)

Any building or structure which is neither listed in the A-Z list nor covered in any occupancy group provided in this Code but unique in character may be categorized in this occupancy by the Board of Appeals. Each and every individual M1 Structure shall be complied with NFPA or equivalent standards for the life and fire safety.

2.1.17.2 Fences, Tanks and Towers (M2)

These shall include fences and boundary walls over 1.5 m high, standalone structures for gravity water tank and towers for telecommunication, power distribution, air-traffic control terminal or observation towers.

2.2 Change of Use

2.2.1Without prior permission from the Authorities having jurisdiction no change shall be made in the type of occupancy or use of any building that would place it in a different occupancy group or in a different subdivision of the same occupancy group. Such changes shall be permitted only when the land use and the building complied with the provisions of this Code and the laws of the land for such group of Occupancy.

2.3 Mixed Occupancy

2.3.1The following occupancies shall not be required to designate as a separated occupancy classification from uses to which they are accessory any occupancy Group other than Occupancy Group J

(a)Assembly rooms having a floor area not more than 75 m².

(b)The administrative and clerical offices and similar offices not exceeding 25 Percent of the floor area of the major occupancy and not related to Hazardous Buildings as defined in Occupancy J.

(c)Administrative offices, gift shops and other similar uses in Occupancy A provided the uses do not exceed 10 Percent of the floor area of the major occupancy.

(d)Kitchens associated with a dining area.

(e)Carports having at least two sides entirely open associated with Occupancy A.

2.3.2 Forms of Occupancy Separations

A building is permitted to have multiple occupancy type, each type of occupancy shall be in groups, which may have combination of different occupancies and shall be separated horizontally or vertically or both accordingly as specified in the Table 3.2.1.

2.3.3 Types of Occupancy Separation

The occupancy separations shall be classified as follows:

(a)Four Hour Fire Resistive: The four hour fire resistive separation wall or slab shall have no unprotected openings therein and shall provide a fire resistance for at least four hour.

(b)Three Hour Fire Resistive: The three hour fire resistive separation wall or slab shall provide a fire resistance of not less than three hour. The total width of all openings in separation wall of any one storey shall not exceed 25 Percent of the length of that wall in that storey and no single opening shall have an area greater than 12 m². The openings shall be protected with a fire resistance assembly doors or windows providing fire resistance of at least three hour.

(c)In case of a floor slab having three hour fire resistance rating, the openings on floor slab shall be protected by vertical enclosures extended above and below such floor openings. The walls of such vertical enclosures shall be at least two hour of fire resistance. All openings in such enclosures shall be protected with fire assembly door or window having fire resistance rating of at least one and one-half hour.

(d)Two Hour Fire Resistive: The two hour fire resistive separation shall be of a construction having a fire resistance rating of not less than two hour. All openings in such separations shall be protected with a fire assembly door or window of a fire protection rating of at least one and one-half hour.

(e)One Hour Fire Resistive: The one hour fire resistive separation shall be of at least one hour fire protection construction. All openings in such separations shall be protected with a fire protection assembly door or window of at least one-half hour fire resistance.

Table 3.2.1: Fire Resistance Rating Requirements for Barrier Walls and

Floor/Ceiling Assemblies between Separated Occupancies (hours)

Table continued (page 11)

2.4 GENERAL REQUIREMENTS OF ALL OCCUPANCIES

2.4.1 Location on Property

2.4.1.1All plots for building construction shall have access to a public road from at least one side.

2.4.1.2Fire separation distance shall be measured from the face of peripheral wall of a building to the adjacent property line. For the purpose of this Section, if a public road adjoining all along a property line shall get the benefit of half of Road width as a part of Fire separation distance. For two or more buildings on the same plot, distances of imaginary lines equidistant from all side of buildings shall be considered as the required fire separation distances.

2.4.1.3The exterior walls of a building shall have a fire resistance and opening protection as specified in Tables 3.3.1 (a), 3.3.1 (b) and 3.2.3.

2.4.1.4Any outward projected elements from the peripheral wall of a building line shall be limited to the sunshade line.

2.4.1.5When openings in exterior walls are required to be protected due to distance from the property line, the aggregate area of such openings shall not exceed 50 Percent of the total area of the wall in each storey.

2.4.1.6Dwellings separation walls in semi-detached or row type development shall comply with Sec 2.4.3.

2.4.2 Allowable Floor Areas

2.4.2.1The total area of the building shall comply with Sec 1.8.3 Chapter 1 of this Part.

2.4.2.2The floor area of the mezzanines shall be included in the area of the respective main floor.

2.4.2.3Floor area calculation shall be divided in to two: (a) All Floor areas at and above the formation level which shall be generally included in the FAR calculation. (b) Floor areas below the formation level shall generally be excluded in FAR calculation provided the Occupancy classifications remain within Utility or Private Garages.

Table 3.2.2: Fire Resistance Ratings in Hours of Exterior Walls for Various Occupancy

Groups

Table continued (page 12)

Table 3.2.3: Requirements for Opening Protection Assembly Based on Fire

Resistance Rating of Exterior Walls

Table continued (page 13)

2.4.3 Permitted Types of Construction

2.4.3.1The types of construction for any occupancy shall conform to the specifications set in Table 3.2.4.

2.4.3.2Common walls in semi-detached or row type development shall not have any unprotected openings and shall be Type I-A construction and all such wall shall comply with requirements of Party wall or Fire wall or Separation wall.

2.4.3.3Ground floor or basement of a building used for car parking and utilities within the barriers by at least three hour fire resistive construction shall be considered as non-separated occupancy provided the building accommodates one or more of the following occupancies:

(i)A3, A5

(ii)E1, F1, F2

(iii)I2, I3, I4

2.4.3.4Entry lobbies, mechanical and electrical rooms and other similar uses incidental to the operation of the building may be provided in the car parking floors provided that the total area of such uses remains within ⅓ (one third) of the parking floor area.

Table 3.2.4: Permitted Types of Construction and Fire Zones for Various

Occupancy Groups

Table continued (page 14)

2.4.4 General Provision for High-Rise Buildings

For the purpose of this Code, a building of any class of Occupancy will be considered as high-rise when it has floors used for human occupancy located more than 33 m from ground level or the lowest level of fire department vehicle access. The provisions of Sec

2.9.6shall be applicable to all such buildings.

2.4.4.1 Maintenance and inspection

All fire protection systems shall be maintained and inspected on a regular basis to keep them in operative condition. The maintenance inspection shall be performed quarterly.

All plumbing installations shall be maintained and inspected periodically to keep them in operative conditions.

2.4.4.2 Type of construction

All high-rise buildings shall be of Type I-A or I-B construction.

2.4.4.3 Fire detection, alarm, evacuation and extinguishment system

All high-rise buildings shall conform to regulations set forth in Part 4 of this Code

2.4.5 Helipads

2.4.5.1 General

Helipads on the roof top of a building or other locations shall be constructed in accordance with this Section.

2.4.5.2 Size

The minimum dimension of the landing area for helicopters weighing less than 1600 kg shall be 6 m × 6 m. There shall be an average clearance of 4 m surrounding and at the

level of the landing area which shall not be less than 2 m at any point.

2.4.5.3 Construction

Helicopter landing areas and supports shall be constructed with non-combustible material.

2.4.5.4 Aviation approval

Before helipads start operating, formal approval shall be obtained from the civil aviation authority.

2.4.6 Universal Accessibility

2.4.6.1All Building (except Occupancies G, H, M and J) shall have universal accessibility as per provisions of this Code.

2.4.6.2Buildings have universal accessibility shall have accessible egress system.

2.5 Requirements For Occupancy A- Residential Buildings

Buildings shall be classified as Occupancy A in accordance with Sec 2.1.5.

2.5.1 Construction, Height and Allowable Area

2.5.1.1Buildings or parts thereof classified as Occupancy A shall be limited to the type of construction set forth in Table 3.2.4 and shall not exceed in area or height as specified in Sections 1.8 and 2.4.2 of this Part.

2.5.1.2Walls and floors separating dwelling units in the same building shall not be less than Type I-D construction.

2.5.1.3Storage or laundry rooms in Occupancy A2, A3, A4 or A5 that are used in common by the occupants shall be at least Type I-D construction.

2.5.1.4When a basement or a ground floor of a building of Occupancy A3 or A5 is used for parking or storage of private cars of the occupants, the parking floor shall be of at least Type I-B construction.

2.5.1.5When the basement or ground floor of a building of Occupancy A is used wholly or partly for generator or electrical substation, the walls and floors surrounding such use shall be of at least Type I-B construction.

2.5.2 Location on Property

Buildings of Occupancy A shall comply with the requirements for location on property and fire resistive exterior walls and openings as specified in this Code.

2.5.3 Access and Exit Facilities and Egress System

2.5.3.1Facilities for access and exit and egress or escape shall comply with the provisions set forth in this Code.

2.5.3.2Every sleeping room in ground, first and second floors shall have at least one operable window or door for emergency escape which shall open directly into the exterior or an interior courtyard. The units shall be operable from the inside without the use of any tool to provide a minimum clear opening of 500 mm width by 600 mm height with a maximum sill height of 1 m above the floor.

2.5.4 Lighting and Ventilation

All buildings or part of a building classified as Occupancy A shall conform to the provisions of Part 3, and Chapters 1 and 3 of Part 8.

2.5.5 Sanitation

Sanitation facilities provided in all Occupancy A buildings shall conform to this Part and Chapter 7 Part 8.

2.5.6 Minimum Dimension of Habitable and Non-habitable Rooms

The minimum dimensions of habitable and non-habitable rooms are specified in Sec

1.12.2Chapter 1 Part 3.

2.5.7 Fire detection, Alarm, Evacuation and Extinguishment

All buildings shall conform to regulations set forth in Part 4 of this Code.

2.5.8 Shaft and Exit Enclosure

Elevator shafts, vent shafts and other vertical openings shall be enclosed conforming to the provisions of Tables 3.3.1 (a) and (b). Exit requirements shall comply with Part 4 of this Code.

2.6 Requirements For Occupancy B - Educational Buildings

Buildings shall be classified as Occupancy B in accordance with Sec 2.1.6.

2.6.1 Construction, Height and Allowable Area

Buildings or parts of buildings classified as Occupancy B shall be limited to type of construction set forth in Table 3.2.4 and comply with the provisions of Sections 1.8 and

2.4.2of this Part to meet the requirements of height and area limitations.

2.6.1.1Rooms or groups of rooms sharing a common space where flammable liquids, combustible dust or hazardous materials are used, stored, developed or handled in an amount exceeding that specified in Sec 2.14.3 shall be classified as Occupancy J. Such rooms or groups of rooms shall comply with the requirements of fire protection as specified in Part 4, Chapters 4 and 5.

2.6.1.2Rooms or groups of rooms, sharing a common space or having separate spaces, served by a common corridor or passage with less than 20 percent outdoor opening of wall in a building of height 11 m or less, or three storeys or less, need not be provided with smoke detectors and standpipe or sprinkler system for fire protection provided it conforms with the access and exit requirements specified in Part 3, Chapter 1, Sec 1.6 and Part 4, Chapters 4 and 5.

2.6.1.3Buildings of Occupancy B situated outside the jurisdiction of any municipality shall have a construction of at least two hours fire resistance.

2.6.2 Location on Property

Buildings of Occupancy B shall comply with the requirements for location on property and fire resistive exterior walls and openings as specified in Sec 2.4.1.

2.6.3 Access and Exit Facilities and Egress System

Facilities for access and exit and Egress system shall comply with the provisions set forth in Sec 1.6, Chapter 1 Part 3 and Chapter 3 Part 4.

2.6.4 Lighting, Ventilation and Sanitation

Lighting, ventilation and sanitation facilities provided in Occupancy Group B buildings shall conform to Sec 1.16, Chapter 1 Part 3 and Chapters 1 and 3 Part 8.

2.6.5 Minimum Dimensions of Class Rooms, Common Toilets and Staircases

The dimension of a class room shall be not less than 4 m on any side and shall have an area of not less than 0.75m² per student. Other provisions for minimum dimensions shall comply with the requirements set forth in Sec 1.8 of Chapter 1 Part 3.

2.6.6 Shaft and Exit Enclosure

Elevator shafts, vent shafts and other vertical openings shall be enclosed conforming to the provisions of Tables 3.3.1 (a) and (b). Exit requirements shall comply with Chapter 3 Part 4.

2.6.7 Fire Detection, Alarm, Evacuation and Extinguishment System

All buildings shall conform to regulations set forth in Part 4 of this Code.

2.7 Requirements For Occupancy C- Institutional Buildings

Buildings shall be classified as Occupancy C in accordance with Sec 2.1.7.

2.7.1 Construction, Height and Allowable Area

The buildings or parts thereof classified as Occupancy C shall be limited to the type of construction set forth in Table 3.2.4 and shall comply with the provisions of Sec 1.8 Chapter 1 Part 3 and Sec 2.4.2 to meet the requirements of height and area limitations.

2.7.2 Location on Property

Buildings of Occupancy C shall comply with the requirements for location on property and fire resistive exterior walls and openings as specified in Sec 2.4.1.

2.7.3 Access and Exit Facilities and Egress System

Facilities for access and exit and egress system shall comply with the provisions set forth in Sec 1.6, Chapter 1 Part 3 and Chapter 3 Part 4.

2.7.4 Lighting, Ventilation and Sanitation

All buildings or part of a building classified as Occupancy C shall conform to the provisions of Sec 1.16, Chapter 1 Part 3 and Chapters 1 and 3, Part 8.

2.7.5 Shaft and Enclosure

Elevator shafts, vent shafts and other vertical openings shall be enclosed conforming to the provisions of Tables 3.3.1 (a) and (b). Exit requirements shall comply with Chapter 3, Part 4.

2.7.6 Fire Detection, Alarm, Evacuation and Extinguishment System

All buildings shall conform to regulations set forth in Part 4 of this Code.

2.8 Requirements For Occupancy D–Health Care Facilities

Buildings shall be classified as Occupancy D in accordance with Sec 2.1.8.

2.8.1 Construction, Height and Allowable Area

The buildings or parts thereof classified as Occupancy D shall be limited to the type of construction set forth in Table 3.2.4 and shall comply with the provisions of Sec 1.8 Chapter 1 Part 3 and Sec 2.4.2 to meet the requirements of height and area limitations.

2.8.2 Location on Property

Buildings of Occupancy D shall comply with the requirements for location on property and fire resistive exterior walls and openings as specified in Sec 2.4.1.

2.8.3 Access and Exit Facilities and Egress System

Facilities for access and exit and egress system shall comply with the provisions set forth in Sec 1.6 Chapter 1, Part 3 and Chapter 3 of Part 4.

2.8.4 Lighting, Ventilation and Sanitation

All buildings or part of a building classified as Occupancy D shall conform to the provisions of Sec 1.16 Chapter 1 Part 3, Chapters 1 and 3 of Part 8.

2.8.5 Shaft and Enclosure

Elevator shafts, vent shafts and other vertical openings shall be enclosed conforming to the provisions of Tables 3.3.1 (a) and (b). Exit requirements shall comply with Chapter 3 of Part 4.

2.8.6 Fire Detection, Alarm, Evacuation and Extinguishment System

All buildings shall conform to regulations set forth in Part 4 of this Code.

2.9 Requirements For Occupancy E–Business

Buildings shall be classified as Occupancy E in accordance with Sec 2.1.9.

2.9.1 Construction, Height and Allowable Area

The buildings or parts thereof classified as Occupancy E shall be limited to the type of construction set forth in Table 3.2.4 and shall comply with the provisions of Sec 1.8 Chapter 1 Part 3 and Sec 2.4.2 to meet the requirements of height and area limitations.

2.9.2 Location on Property

Buildings of Occupancy E shall comply with the requirements for location on property and fire resistive exterior walls and openings as specified in Sec 2.4.1.

2.9.3 Access and Exit Facilities and Egress System

Facilities for access and exit and egress system shall comply with the provisions set forth in Sec 1.6 Chapter 1 Part 3, Chapter 3 of Part 4.

2.9.4 Lighting, Ventilation and Sanitation

All buildings or part of a building classified as Occupancy E shall conform to the provisions of Sec 1.16 Chapter 1 Part 3, Chapters 1 and 3 of Part 8.

2.9.5 Shaft and Enclosure

Elevator shafts, vent shafts and other vertical openings shall be enclosed conforming to the provisions of Tables 3.3.1 (a) and (b). Exit requirements shall comply with Chapter 3 of Part 4.

2.9.6 Fire Detection, Alarm, Evacuation and Extinguishment System

All buildings shall conform to regulations set forth in Part 4 of this Code.

2.10 Requirements For Occupancy F–Mercantile Buildings

Buildings shall be classified as Occupancy F in accordance with Sec 2.1.10.

2.10.1 Construction, Height and Allowable Area

The buildings or parts thereof classified as Occupancy F shall be limited to the type of construction set forth in Table 3.2.4 and shall comply with the provisions of Sec 1.8, Chapter 1 of Part 3 and Sec 2.4.2 to meet the requirements and limitations of height and area.

2.10.2 Location on Property

Buildings of Occupancy F shall comply with the requirements for location on property and fire resistive exterior walls and openings as specified in Sec 2.4.1.

2.10.3 Access and Exit Facilities and Emergency Escapes

Facilities for access and exit and emergency escape shall comply with the provisions set forth in Sec 1.6 Chapter 1 Part 3 and Chapter 3 Part 4.

2.10.4 Lighting, Ventilation and Sanitation

All buildings or part of a building classified as Occupancy F shall conform to the provisions of Sec 1.16 Chapter 1 Part 3, Chapters 1 and 3, Part 8.

2.10.5 Shaft and Enclosure

Elevator shafts, vent shafts and other vertical openings shall be enclosed conforming to the provisions of Tables 3.3.1 (a) and (b). Exit requirements shall comply with Chapter 3, Part 4.

2.10.6 Fire Detection, Alarm, Evacuation and Extinguishment System

All buildings shall conform to regulations set forth in Part 4 of this Code.

2.10.7 Special Hazards

Installations which are discharging exhaust, heating apparatus, boiler and central heating/air-conditioning plant shall conform to the provisions of this Code as specified in this Code.

2.11 Requirements For Occupancy G–Industrial Buildings

Buildings shall be classified as Occupancy G in accordance with Sec 2.1.11. A non-exhaustive and indicative list of low hazard and moderate hazard industrial uses are listed in A to Z list. Storage and use of hazardous materials shall not exceed the exempt amount specified in Sec 2.14.3.

2.11.1 Construction, Height and Allowable Area

The buildings or parts thereof classified as Occupancy G shall be limited to the type of construction set forth in Table 3.2.4 and shall comply with the provisions of Sec 1.8 of Chapter 1, Part 3 and Sec 2.4.2 to meet the requirements and limitations of height and floor area.

The ceiling height of the production area, shall confirm to the minimum volume required per workers as specified by the Bangladesh Labor Act, 2006 and other laws of the land. In any case the ceiling height and the head room clearance of a production floor shall not be less than 3.3 meter and 2.286 meter respectively.

2.11.2 Location on Property

Buildings of Occupancy G shall comply with the requirements for location on property and fire resistive exterior walls and openings as specified in Sec 2.4.1.

2.11.3 Access and Exit Facilities and Egress System

Facilities for access and exit and emergency escape shall comply with the provisions set forth in Sec 1.6 Chapter 1, Part 3 and Chapter 3, Part 4.

2.11.4 Lighting, Ventilation and Sanitation

All buildings or part of a building classified as Occupancy G shall conform to the provisions of Sec 1.16 Chapter 1, Part 3 and Chapters 1 and 3, Part 8. Industrial buildings having roof opening for day lighting and natural ventilation shall comply with the following requirements:

(a)The aggregate opening in roof and external windows shall not be less than 10 Percent of the floor area.

(b)For natural ventilation by means of exterior window openings, the operable window area shall not be less than 5 Percent of the total floor area.

Exception:

Industrial buildings wherein artificial lighting and mechanically operated ventilation systems of approved quality are installed, need not be provided with natural ventilation or natural lighting.

2.11.5 Shaft and Enclosure

Elevator shafts, vent shafts and other vertical openings shall be enclosed conforming to the provisions of Tables 3.3.1 (a) and (b). Exit requirements shall comply with Chapter 3, Part 4.

2.11.6 Fire Detection, Alarm, Evacuation and Extinguishment System

All buildings shall conform to regulations set forth in Part 4 of this Code.

2.11.7 Special Hazards

Chimneys, vents and ventilation ducts shall be constructed with noncombustible materials. Every bailer, central heating plants, electrical rooms, or hot water supply boiler shall be separated from the rest of the occupancy or use by not less than two hour fire resistive construction.

2.12 Requirements For Occupancy H–Storage Buildings

Buildings shall be classified as Occupancy H in accordance with Sec 2.1.12.

2.12.1 Construction, Height and Allowable Area

The buildings or parts thereof classified as Occupancy H shall be limited to the type of construction set forth in Table 3.2.4 and shall comply with the provisions of Sec 1.8 of Chapter 1, Part 3 and Sec 2.4.2 to meet the requirements of height and area limitations.

2.12.2 Location on Property

The location on property for Occupancy H shall conform to Sec 2.4.1.

2.12.3 Access and Exit Facilities and Egress System

Facilities for access and exit and egress system shall comply with the provisions set forth in Sec 1.6 of Chapter 1, Part 3 and Chapter 3, Part 4.

2.12.4 Lighting, Ventilation and Sanitation

All buildings or part of a building classified as Occupancy H shall conform to the provisions of Sec 1.16 of Chapter 1 Part 3, Chapters 1 and 3, Part 8.

2.12.4.1 Special provision

The provisions of Sec 1.16, does not apply to non-habitable spaces of H1 and H2 occupancies unless otherwise required by this Code. Ventilators of size not less than 0.25 m² shall be provided where suitable 0.30 m above the floor level for floor level ventilators and 0.30 m below the roof level for roof level ventilators. There shall be one floor level ventilator and one roof level ventilator for every 0.25 m² of the floor area. Mechanized ventilation system of approved quality shall be installed where required.

2.12.4.2Though inhabitable, the minimum air quality of such indoor spaces shall be maintained in a way that it does not pose any health hazard to the occasional users of that space.

2.12.5 Shaft and Enclosure

Elevator shafts, vent shafts and other vertical openings shall be enclosed conforming to the provisions of Tables 3.3.1 (a) and (b). Exit requirements shall comply with Chapter 3, Part 4.

2.12.6 Fire Detection, Alarm, Evacuation and Extinguishment System

All buildings shall conform to regulations set forth in Part 4 of this Code.

2.12.7 Special Hazards

The storage of hazardous materials shall not exceed the exempt amount as specified in Table 3.2.5. The storage of moderate and low hazardous materials shall be separated at least by a two hour fire resistive construction.

2.13 Requirements For Occupancy I–Assembly Buildings

Buildings shall be classified as Occupancy I in accordance with Sec 2.1.13.

2.13.1 Construction, Height and Allowable Area

The buildings or parts thereof classified as Occupancy I shall be limited to the type of construction set forth in Table 3.2.4 and shall comply with the provisions of Sec 1.8 Chapter 1 Part 3 and Sec 2.4.2 to meet the requirements and limitations of height and area.

2.13.2 Location on Property

Buildings of Occupancy I shall comply with the requirements for location on property and fire resistive exterior walls and openings as specified in Sec 2.4.1.

2.13.3 Access and Exit Facilities and Egress System

Facilities for access and exit and Egress system shall comply with the provisions set forth in Sec 1.6 Chapter 1 of Part 3 and Chapter 3 of Part 4 and universally accessibility as per provisions of this Code.

2.13.4 Lighting, Ventilation and Sanitation

All buildings or part of a building classified as Occupancy I shall conform to the provisions of Sec 1.16 Chapter 1 Part 3, Part 3 and Chapters 1 and 3, Part 8.

2.13.5 Shaft and Enclosure

Elevator shafts, vent shafts and other vertical openings shall be enclosed conforming to the provisions of Tables 3.3.1 (a) and (b). Exit requirements shall comply with Chapter 3, Part 4.

2.13.6 Fire Detection, Alarm, Evacuation and Extinguishment System

All buildings shall conform to regulations set forth in Part 4 of this Code.

The specification of this Section shall apply to all parts of buildings and structures that contain stages or platforms and other similar appurtenances as herein defined.

(a)Stages: A stage is a three side enclosed or partially enclosed portion of a building which is designed or used for presentation of plays or lectures or other entertainment. A stage shall be further classified as legitimate stage, regular stage and thrust stage.

(b)Stage, Legitimate: A stage wherein curtains, drops, leg drops, scenery, lighting devices or other stage effects are adjustable horizontally or vertically or suspended overhead.

(c)Stage, Regular: A stage wherein curtains, fixed drops, valances, scenery and other stage effects are suspended and are not adjustable or retractable.

(d)Stage, Thrust: A stage or platform extended beyond the proscenium line and into the audience.

2.13.6.1 Legitimate Stage

Legitimate stage shall be constructed as specified in Part 4, specifying the type of construction but shall not be less than construction Type I-C. The position of the legitimate stage extending beyond the proscenium opening line shall be permitted to be constructed with two hour fire-resistive materials. The floor of the stage may be constructed with one hour fire rating materials. Thickness of a wooden floor shall not be less than 50 mm.

2.13.6.2 Regular and Thrust Stages

Regular stages and thrust stages shall be constructed by not less than two hour fire resistive materials. Wooden floor when required in a stage shall not be less than 50 mm in thickness with one hour fire resistive rating.

2.13.6.3 Trap doors

All trap doors and any other opening in stage floors shall be equipped with tight fitting solid wood trap doors with thickness not less than 50 mm.

2.13.6.4 Stage rigging loft

The grid iron frame in the loft, housing lighting and audio equipment, all the machinery for flying scenery and fly galleries, along with their installations, shall be constructed of approved noncombustible materials.

2.13.6.5 Foot lights and stage electrical equipment

Foot lights and border lights shall be installed in a protective cover constructed of noncombustible materials.

2.13.6.6 Trim, finish and decorative hangings

All materials used in moulding and decoration around the proscenium shall be of approved noncombustible materials.

2.13.6.7 Proscenium curtain

The proscenium curtain shall be of approved fire retardant material and shall protect against passage of flame and smoke for at least 30 minutes.

2.13.7 Motion Picture Projection Rooms

2.13.7.1Every projection room shall be constructed in conformity with the construction requirements for the type of the building in which the projection room is located. The wall opening required for projection need not have a fire protection assembly but shall be closed with glass or other approved materials.

2.13.7.2The floor area of a projection room shall not be less than 8 m² for a single machine. The working space between the machines when more than one machine is used shall not be less than 0.75 m.

2.13.7.3The height of the projection room shall have a minimum clear space of 2.5 m.

2.13.8 Sports Facilities

2.13.8.1 Vomiters, aisles and exits of seating galleries

Tunnels, aisles and exits of galleries shall be constructed conforming to the following requirements.

(a)There shall be a minimum of two exits remotely located from each other immediately to the outside for each balcony or tier. There shall be at least three exits when seating capacity exceeds 1000 persons and four exits when it exceeds 4000 persons. For every additional 1000 persons the exit shall be designed to accommodate provision (f) given below.

(b)There shall be at least 0.6 m2 of space per person in the gallery. Minimum width considered for a seat in the gallery shall be 0.45 m.

(c)There shall be a maximum of 33 seats on each side of any aisle. Minimum width of the main aisles and the secondary aisles shall be 1.0 m and 0.7 m respectively.

(d)Entrance and exits shall be protected by safety railings.

(e)Back to back space between two rows of seats shall not be less than 0.80 m.

(f)The evacuation time in the galleries shall not be more than 10 minutes.

(g)All tunnels, aisles and exits shall conform to safety guidelines for means of escape set forth in Part 4.

(h)One percent of the total seat capacity shall have provisions for accommodation with universal accessibility at the approach or exit level.

2.13.8.2 Swimming pools

Any swimming pool used or constructed for exclusive use by Occupancy A1 and is available only to the occupants and private guests shall be classified as a private swimming pool. Any swimming pool other than private swimming pool shall be classified as a public swimming pool. Swimming pools shall be constructed in conformity with the following requirements.

(a)There shall be at least 1.5 m space between any sides of a swimming pool and a rear or side property line. For street property lines, this distance shall be at least 2.0 m.

(b)Swimming pools shall be provided with overflow provision to remove scum and other materials from the surface of the water. When water skimmers are used for private pools there shall be one skimming device for each 50 m2 of surface area or fraction thereof.

(c)The overflow gutters shall not be less than 75 mm deep and shall be pitched to slope of one unit vertical to 50 units horizontal (1:50) toward drains.

(d)Public swimming pools shall be so designed that the pool water turnover is at least once every 8 hours.

(e)Private swimming pools shall be designed so that there is a pool water turnover at least once every 18 hours.

(f)Public swimming pools shall be equipped with filters, the capacity of which shall be controlled to filter 140 liters per minute per m2 of surface area. Private swimming pool filters shall not filter more than 230 liters per minute per m2 of the surface area.

(g)The pH value of the pool water shall be between 7.0 and 7.5.

(h)All recirculation systems shall be equipped with an approved hair and lint strainer installed in the system ahead of the pump.

(i)All swimming pool and equipment shall be designed to be emptied completely of water and the discharged water shall be disposed in an approved manner and shall not create problems in the neighboring property.

(j)Pumps, filters and other mechanical and electrical equipment shall be placed in enclosed spaces and shall not be accessible to the bathers.

(k)Used water from the pool when being discarded shall be reused as grey water for the building and its premises as per provision of Appendix G.

2.13.9 Amusement Building Fire Protection System

The fire protection system shall be as per provisions of this Code.

2.14 Requirements For Occupancy J–Hazardous Buildings

Buildings shall be classified as Occupancy J in accordance with Sec 2.1.14.

2.14.1 General

The plans for buildings and structures accommodating Occupancy J shall clearly indicate the type and intended use of materials and its processing or handling methods so as to reflect the nature of use of each portion of such buildings.

2.14.1.1 Occupancy J1

Any building or portion thereof containing any of the following items more than exempted quantity shall be classified as Occupancy J1.

(a)Combustible dusts and any similar solid material sufficiently comminuted for suspension in still air which, when so suspended, is capable of self-sustained combustion.

(b)Combustible liquids - Any liquid having a flash point at or above 40°C shall be known as class II and class III liquids. Combustible liquids shall be classified as follows:

(i)Liquids having flash point at or above 40°C and below 60°C.

(ii)Liquids having flash points at or above 60°C and below 95°C.

(c)Cryogenic liquids (flammable or oxidizing): Any liquid that has a boiling point below -130°C.

(d)Flammable Gases: Any gas when mixed with air in a proportion of 13% (by volume) forms a flammable mixture under atmospheric temperature and pressure.

(e)Flammable Liquids: Any liquid that has a flash point below 40°C and has a net vapour pressure exceeding 275 kPa at 40°C. Flammable liquids shall be known as Class I liquid and shall be further classified as follows:

(i)Liquids having flash point below 25°C and having a boiling point below 40°C.

(ii)Liquids having flash point below 25°C and having a boiling point at or above 40°C.

(iii)Liquids having flash points at or above 25°C and below 40°C.

(f)Oxidizers class 3: As determined in accordance with NFPA 43A.

(g)Oxidizing gases: As determined in accordance with NFPA 43C.

(h)Pyrophoric liquids, solids and gases that will ignite spontaneously in air at a temperature of 55°C or below.

(i)Unstable (reactive) materials class 3, non-detonable as determined in accordance with NFPA 704.

(j)Combustible fibers: Includes readily ignitable fibers like cotton, sisal, jute hemp, tow, cocoa fiber, oakum, baled waste, baled waste paper, kapok, hay, straw, excelsior, Spanish moss and other similar materials.

(k)Flammable solid: Any solid including blasting agent or explosive that is liable to cause fire through absorption of moisture, spontaneous chemical change or retained heat from manufacturing or processing, or which when ignited burns so vigorously and persistently as to create a serious hazard.

(l)Organic peroxides, Class II and Class III as determined in accordance with NFPA 43B.

(m)Oxidizers Class I and Class II as determined in accordance with NFPA 43A.

(n)The bulk storage of unstable (reactive) materials Class 1 and Class 2 as determined in accordance with NFPA 704, water reactive materials, Class 2 and Class 3 which react with water to release a gas that is either flammable or present a health hazard as determined in accordance with NFPA 704.

2.14.1.2 Occupancy J2

Any building or portion thereof containing the following shall be classified as Occupancy J2:

(a)Corrosives: Any substance that causes visible destruction of or irreversible alteration in living tissues by chemical action at the site of contact.

(b)Highly toxic materials: The materials falling in this category are as follows:

(i)Oral Toxicity: A chemical that has a median lethal dose of 50 mg or less per kg of body weight when administered orally to albino rats weighing between 200 and 300 gm each.

(ii)Toxicity of Inhalation: A chemical that has a median lethal concentration in air of 200 ppm or less by volume of gas or vapors, or 2 mg per liter or less of mist, fume or dust, when administered by continuous inhalation for 1 hour (or less if death occurs within 1 hour) to albino rats weighing between 200 and 300 grams each.

(iii)Toxicity by Skin Absorption : A chemical that has median lethal dose of 200 mg or less per kg of body weight when administered by continuous contact for 24 hours (or less if death occurs within 24 hours) with the bare skin of albino rabbits weighing between 2 and 3 kg each.

(iv)Irritants: Any noncorrosive chemical or substance which causes a reversible inflammatory effect on living tissues by chemical action at the site of contact.

(v)Radioactive Material: Any material or combination of materials that spontaneously emit ionizing radiation.

(vi)Sensitizers: A chemical or substance that causes a substantial proportion of exposed people or animals to develop an allergic reaction in normal tissue after repeated exposure.

(c)The Occupancy J2 shall also include among others the followings:

(i)Dry cleaning establishments using flammable solvents.

(ii)Explosive manufacturing.

(iii)Paint or solvent manufacturing (flammable base).

(iv)Pyrexin plastic manufacturing.

(v)Sodium nitrate or ammonium nitrate.

(vi)Storage of combustible film.

2.14.1.3 Occupancy J3

Any building or portion thereof which is used for storage, handling, processing or manufacture of materials and products that use biological processes and in which the risk of harmful biological threat to the occupants exist, shall comply with the guidelines specified by the Department of Health.

2.14.1.4 Occupancy J4

Any building or portion thereof which is used for storage, handling, processing or manufacture of materials and products that use nuclear and radioactive processes and in which the risk of radioactive contamination exists, shall comply with the guidelines specified by Bangladesh Atomic Energy Commission.

2.14.2 Special Provisions

2.14.2.1The following shall not be included in Occupancy J but shall be classified in the occupancy group which they most nearly resemble and such classification shall be approved by the Authority:

(a)All buildings and structures and parts thereof which contain less than the exempt quantities as specified in Table 3.2.5, when such buildings comply with the fire protection provisions of this Code.

(b)Rooms containing flammable liquid in lightly closed containers of 4 litre capacity or less for retail sales or private use on the premises and in quantities not exceeding 820 litres/m² of room area.

(c)Retail paint sales rooms with quantities not exceeding 820 litres/m² of room area.

(d)Closed systems housing flammable or combustible liquids or gases used for the operation of machinery or equipment.

(e)Cleaning establishments.

(f)Liquor stores and distributors without bulk storage.

(g)Tire storage containing less than 10,000 vehicle tires.

(h)The storage or use of materials for agricultural purposes for use on the premises.

(i)Pyrophoric solids or liquids not exceeding 3 m3 in storage cabinet located in a building that is equipped throughout with an automatic sprinkler system provided in accordance with the fire protection provisions of this Code.

(j)Pyrophoric solids or liquids not exceeding 3 kg in storage cabinet located in a building that is provided with an automatic sprinkler system installed in accordance with the fire protection provisions in accordance to Part 4 of this Code.

(k)Class 2 water reactive materials not exceeding 100 kg in an approved storage cabinet located in a building that is provided with automatic sprinkler installed in accordance with the fire protection provisions in accordance to Part 4 of this Code.

2.14.3 Construction, Height and Allowable Area

2.14.3.1The buildings or parts thereof classified as Occupancy J shall be limited to the type of construction set forth in Table 3.2.4 and shall comply with the provisions of Sec

1.8of Chapter 1, Part 3 and Sec 2.4.2 of this Chapter to meet the requirements of height and area limitations.

2.14.3.2Floors: The floors and spaces containing hazardous materials and in areas where motor vehicles, boats, helicopters or airplanes are stored, repaired or operated shall be of noncombustible, liquid-tight construction.

Exception: In floors and areas where no repair works are carried out may be surfaced or waterproofed with asphaltic paving materials.

2.14.3.3Spill Control: The floors containing hazardous repair or other works shall be recessed a minimum of 100 mm so as to prevent flow of liquids to adjoining areas.

2.14.3.4Drainage: The buildings and areas shall be provided with approved drainage system to direct the flow of liquids to an approved location or room or area designed to provide secondary containment of the hazardous materials and fire protection water.

Table 3.2.5(a): Exempted Amount of Hazardous Materials in Terms of Physical

Hazard in a Control Area

Table continued (page 32)

Table continued (page 33)

Table continued (page 34)

Table 3.2.5(c): Location and Number of Control Areas

Table 3.2.5(c): Location and Number of Control Areas

2.14.3.5The drains shall be designed with adequate slope and section to carry the design discharge of the sprinkler system. The material used in the drains shall be suitable for drainage of the storage materials.

2.14.3.6Separate drainage system shall be designed for materials which react with each other producing undesirable results. They may be combined when they have been provided with approved means of discharge into the public sewer or natural stream or river.

2.14.3.7Containment: The outflow from the drains shall be directed to a containment system or other area that provide a secondary storage for the hazardous materials and liquids and fire protection water. The containment capacity shall be capable of containing the outflow from the drains for a period of at least one hour.

2.14.3.8The overflow from secondary containment system shall be directed to a safe location away from the building, adjoining properties and storm drain.

2.14.3.9If the secondary containment storage area is open to rainfall it shall be designed to accommodate 24 hour rainfall or a continuous rainfall of 100 mm per day.

2.14.3.10Smoke and Heat Vents: Smoke and heat vents shall be provided in areas or rooms containing hazardous materials exceeding the exempt amount of Table 3.2.5.

2.14.3.11Standby Power: Standby power shall be provided in the occupancies where Class I, II or III organic peroxides are stored.

2.14.4 Location on Property

The location on property for Occupancy J shall conform to Sec 2.4.1 and Part 4.

2.14.5 Access and Exit Facilities and Emergency Escapes

Facilities for access and exit and emergency escape shall comply with the provisions set forth in Sec 1.6 of Chapter 1, Part 3, and Chapter 3, Part 4.

2.14.6 Lighting and Ventilation

2.14.6.1All spaces and rooms customarily occupied by human beings shall be provided with natural light by means of exterior glazing with an area of not less than 10 Percent of the floor area. Such rooms and spaces shall be provided with natural ventilation by means of exterior openings with an open able area not less than 5 Percent of the total floor area or artificial light and mechanically operated ventilation system as per provisions of this Code.

2.14.6.2Ventilation in Hazardous Locations: The rooms, spaces or areas where explosive, corrosive, combustible, flammable or highly toxic dust, mists, fumes, vapors or gases are stored or may be emitted due to the processing, use, handling or storage of materials shall be mechanically ventilated.

2.14.6.3The mechanical ventilation of all hazardous uses shall be segregated or separated from the ventilation of other areas. The emissions generated at work areas shall be confined to the area in which they are generated and shall be removed or discharged outside the building and preventive measures against back flow of such hazardous fumes or gases inside the building shall be installed.

2.14.6.4Ventilation of Toilets: Toilets shall be provided with fully openable exterior window of at least 0.3 m² in area or a vertical duct not less than 62500 mm² in cross-section for the first water closet, with additional 31250 mm² for each additional fixture or a mechanically operated exhaust system equipped to provide a complete change of air in every 15 minutes. Such system shall be connected to the outside air and the point of discharge shall be at least 1.0 m away from any other opening into the building.

2.14.6.5Other requirements of water closets are specified in Sec 1.12.4 Chapter 1, Part 3.

2.14.7 Sanitation

All buildings or part of a building classified as Occupancy J shall conform to the provisions of Sec 1.16 of this Chapter and Part 8 of this Code.

2.14.8 Shaft and Exit Enclosures

Elevator shafts, vent shafts and other vertical openings shall be enclosed conforming to the provisions of Tables 3.3.1 (a) and (b). Exit requirements shall comply with Chapter 3, Part 4.

2.14.9 Fire Detection, Alarm, Evacuation and Extinguishment System

All buildings shall conform to regulations set forth in Part 4 of this Code.

2.14.10 Explosion Control

Explosion control, equivalent protective devices or suppression systems or barricades shall be installed to control or vent the gases resulting from deflagrations of dusts, gases or mists in a room or area, building or other enclosures to minimize structural or mechanical damage.

Walls, floors and roofs separating a use from explosion exposure shall be designed according to the provisions of Chapter 1, Part 6.

Explosion venting shall be designed in exterior walls or roof only. The venting shall be provided to prevent serious structural damage and production of lethal projectiles. The venting design shall recognize the natural characteristics and behaviors of building materials in an explosion. The vents shall be designed to relieve at a maximum internal pressure of 1.0 kPa but not less than the loads required by Chapter 2, Part 6. One or more of the following systems shall be installed to relieve explosion, where applicable:

(a)Lightweight materials in walls

(b)Light fastening devices with hatch covers

(c)Light fastening with outward opening swing doors in exterior walls

(d)Nonbearing walls with light ties

The venting devices shall discharge vertically or horizontally directly to an unoccupied yard having a width of not less than 16 m on the same plot.

The releasing devices shall be so located that the discharge end shall not be less than 3 m vertically and 6 m horizontally from window openings or exits in the same or adjoining buildings.

2.14.11 Special Hazard

Chimneys, vents and ventilation ducts shall be of noncombustible materials.

All boilers, central heating plants, electrical rooms or hot water supply boiler shall be separated from the rest of the occupancies or uses by not less than 2 hour fire resistive construction.

The devices that generate a spark, flame or glow capable of igniting gasoline shall not be installed or used within 0.5 m of the floor.

Equipment or machinery that produces or emits combustible or explosive dust or fibers shall be provided with an approved dust collecting and exhaust system.

The equipment or systems that are used to collect or process or convey combustible dust or fibers shall be installed with explosion venting or containment system.

2.15 Requirements For Occupancy K–Garage Buildings

Buildings shall be classified as Occupancy K in accordance with Sec 2.1.15.

Exception: Non-separated use mentioned in Sec 2.3.1.

2.15.1 Construction, Height and Allowable Area

The buildings or parts thereof classified as Occupancy K shall be limited to the type of construction set forth in Table 3.2.4 and Sec 2.4.4.2 and shall comply with the other provisions of Sec 1.8 Chapter 1 Part 3, Appendix F and Sec 2.4.2 to meet the requirements and limitations of height and area. With the exceptions mentioned in Sec 2.4.3, all garage floors shall be constructed with not less than 4 hour fire resistance materials.

2.15.1.1Floors: The floors and spaces where motor vehicles are stored, repaired or operated shall be of noncombustible, liquid-tight construction.

Exception: In floors and areas where no repair works are carried out may be surfaced or waterproofed with asphaltic paving materials.

2.15.1.2Spill Control: The floors containing hazardous repair or other works shall be recessed a minimum of 100 mm so as to prevent flow of liquids to adjoining areas.

2.15.1.3Drainage: The buildings and areas shall be provided with approved drainage system to direct the flow of liquids to an approved location or room or area designed to provide secondary containment of the hazardous materials and fire protection water.

The drains shall be designed with adequate slope and section to carry the design discharge of the sprinkler system. The material used in the drains shall be suitable for drainage of the storage materials.

The quality of discharged liquids must attain approved level before discharging into the public sewer or natural stream or river.

2.15.1.4Smoke and Heat Vents: Smoke and heat vents shall be provided in areas or rooms containing hazardous materials exceeding the exempt amount of Table 3.2.5.

2.15.2 Location on Property

Buildings of Occupancy K shall comply with the requirements for location on property and fire resistive exterior walls and openings as specified in Sec 2.4.1.

2.15.3 Access and Exit Facilities and Emergency Escapes

Facilities for access and exit and emergency escape shall comply with the provisions set forth in Sec 1.6 Chapter 1 Part 3, Chapter 3 Part 4 and Appendix F.

2.15.4 Lighting, Ventilation and Sanitation

All buildings or part of a building classified as Occupancy K shall conform to the provisions of Sec 1.16 Chapter 1 Part 3, Chapters 1 and 3, Part 8.

2.15.5 Shaft and Enclosure

Elevator shafts, vent shafts and other vertical openings shall be enclosed conforming to the provisions of Tables 3.3.1 (a) and (b). Exit requirements shall comply with Chapter 3 Part 4.

2.15.6 Fire Detection, Alarm, Evacuation and Extinguishment System

All buildings shall conform to regulations set forth in Part 4 of this Code.

2.16 Requirements For Occupancy L–Utility Buildings

Buildings shall be classified as Occupancy L in accordance with Sec 2.1.16.

2.16.1 Construction, Height and Allowable Area

The buildings or parts thereof classified as Occupancy L shall be limited to the type of construction set forth in Table 3.2.4 and Sec 2.4.3, and shall comply with the provisions of Sec 1.8 Chapter 1 Part 3, and Sec 2.4.2 to meet the requirements and limitations of height and area.

2.16.2 Location on Property

Buildings of Occupancy L shall comply with the requirements for location on property and fire resistive exterior walls and openings as specified in Sec 2.4.1.

2.16.3 Access and Exit Facilities and Egress System

Facilities for access and exit and egress system shall comply with the provisions set forth in Sec 1.6 Chapter 1 Part 3 and Chapter 3 Part 4.

2.16.4 Lighting, Ventilation and Sanitation

All buildings or part of a building classified as Occupancy L shall conform to the provisions of Sec 1.16 Chapter 1 Part 3, Chapters 1 and 3, Part 8.

2.16.5 Shaft and Enclosure

Elevator shafts, vent shafts and other vertical openings shall be enclosed conforming to the provisions of Tables 3.3.1 (a) and (b). Exit requirements shall comply with Chapter 3 Part 4.

2.16.6 Fire Detector, Alarm, Evacuation and Extinguishment System

All buildings shall conform to regulations set forth in Part 4 of this Code.

2.16.7 Special Hazard

2.16.7.1Since the nature of use of this occupancy involves hazard, special consideration for maintenance and operational safety must be ensured. Depending upon the degree of hazard involved, this occupancy type may have separate and isolated structure.

2.16.7.2Chimneys and vents and ventilation ducts shall be of noncombustible materials.

All boilers, central heating plants, electrical rooms or hot water supply boiler shall be separated from the rest of the occupancies or uses by not less than 2 hour fire resistive construction.

The devices that generate a spark, flame or glow capable of igniting gasoline shall not be installed or used within 0.5 m of the floor.

Equipment or machinery that produces or emits combustible or explosive dust or fibers shall be provided with an approved dust collecting and exhaust system.

The equipment or system that is used to collect or process or convey combustible dust or fibers shall be installed with explosion venting or containment system.

2.17 Requirements For Occupancy M–Miscellaneous Buildings

Buildings shall be classified as Occupancy M in accordance with Sec 2.1.17.

2.17.1 General

The buildings or parts thereof classified as Occupancy M shall be limited to the type of construction set forth in Table 3.2.4 and shall comply with the requirements of Sections

1.8and 2.4.2 to meet the requirements of height and area limitations.

Any building or portion thereof that exceeds the limitations provided in this Chapter shall be classified in the occupancy group other than M that it most nearly resembles.

2.17.2 Location on Property

The location on property for Occupancy M shall conform to Sec 2.4.1.

2.17.3 Access and Exit Facilities and Emergency Escapes

Access and exit facilities for Occupancy M shall comply with the specification set in Sec

1.6Chapter 3, Part 4.

2.17.4 Lighting, Ventilation and Sanitation

All buildings or part of a building classified as Occupancy M shall conform to the provisions of Sec 1.16 Chapters 1 and 3, Part 8.

2.17.5 Shaft and Exit Enclosures

Elevator shafts, vent shafts and other vertical openings shall be enclosed conforming to the provisions of Tables 3.3.1 (a) and (b). Exit requirements shall comply with the requirements of Chapter 3, Part 4.

2.17.6 Fire Detection, Alarm, Evacuation and Extinguishment System

All buildings shall conform to regulations set forth in Part 4 of this Code.

Table 3.2.6: A – Z List of Occupancy Classification

Use or OccupancyBrief DescriptionOccupancy Class/Sub-class
A
Adhesives manufactureExcluding manufacture of basic componentsG or J depending on nature of materials involved
Advertising displays manufactureG
Agricultural machinery manufactureIncluding repairsG
AgricultureWithout nuisance or sales limitationH
AgriculturalSmall farm house, (limited to storage quantity)F
H or J
Large farm house, storage quantity unlimited
G
Small grain processing unit, (limited to quantity)
G or J
Large grain processing unit, quantity unlimited
Aircraft manufacture (including parts)G or J depending on nature of materials and process involved
AirportsMIXED USE (depending on detail requirement)
Amusement parks, children's(See children's amusement parks)-
Amusement park activitiesI
AnimalAnimal hospitalsF
Animal pound (for stray and lost animal)H
Animal crematoriumG
Killing establishments, for retail salesF
Slaughtering, processing and packingG
Antique storesF
Apartments(see residential)A
in walkup buildings
In high risesA
in housing complexA
Apartment hotelsA5
Apparel(See clothing)
AppliancesElectrical appliance ManufacturingG
Television, radio, phonograph or household appliance stores, (Limited as to floor areas)F
F
Television, radio, phonograph or household appliance stores, (Unlimited)
F
Household appliance repair shops
Arenas, auditoriums, or stadiumsSee Assembly (Limited as to capacity)I
See Assembly (Unlimited)I
Art GalleriesCommercial (sales included)F
With exhibition open to public viewing for limited period (sales included)I
Art goods manufacture, religious temple or church, excluding foundry operationsG
Art metal craft shopsF
Art needle workSix occupants or lessNon-separated use to A1 and A2 Occupancy
More than six occupants (see industrial)
G
Artist's supply storesF
Asphalt or asphalt productsManufactureJ
AssemblyLarge assembly with fixed seatsI1
Small assembly with fixed seatsI2
Large assembly without fixed seatsI3
Small assembly without fixed seatsI4
For sport facilitiesI5
Athletic equipment manufactureG
Athletic goods storesF
Auctions rooms, open to publicI
AuditoriumsSee assemblyI
Automatic laundriesG
AutomobilesDead StorageH
Driving SchoolsE
Glass or mirror shopsF
WashingK
Manufacture, including parts, orJ
engine rebuilding
K
Rental establishments
Repairs, bodyK
Repairs, without body repairsK
Sales open or enclosedK
Seat cover or convertible topF
establishments, selling or installation
K
Showrooms, no repair services
Supply stores, no repair servicesF
Tire sales establishments, limited toF
quantity
J
Tire sales establishments, unlimited
Wrecking establishmentsG
Automotive serviceLimited as to total areaK
stations
Unlimited...K
AwningsCustom shopsH
Manufacture, with no limitation onG
production or on floor area
B
BakeriesHome-made, six or less occupants (baking included)non-separated use to main occupancy
Large scale, more than six occupants (baking included)G
F
Sales only
Banks,Including drive-in banksE
Banquet hallsI
Bar, alcoholicI
Barber shopsF
BarnsH
Barracks(See residential)A4
Baths, steamI
Beaches, commercialNot applicable
Beauty parlorsF
BeveragesBottling worksG
Manufacture, AlcoholicJ
Non-alcoholicG
BicycleManufactureG
Rental or repair shopsF
SalesF
Billiard parlorsI
Blacksmith shopssmall scale (limited to six occupants), repair or makingF
G
Unlimited
Blueprinting establishmentsdrawing printingG
Boarding houses(See residential)A
BorstalsC
BoatelsA
Boats or shipsBailer works at port or dockJ
BreakingJ
Building or repair, for boats less than 200 ft. in lengthJ
Building or repair, for boats 200 ft. or more in lengthJ
Docks, for small pleasure boatsNot applicable
Fuel sales, open or enclosedF
Un- restricted as to location
Restricted as to locationJ
Rentals opened or enclosedF
Sales opened or enclosedF
Showrooms, with no repair services..F
Storage, repair, or painting, including the incidental sales of boats, boat parts, or accessories, with restrictions on boat size and setbacksG
Bone distillationG or J depending on process or material used
Botanical garden structuresM
BookBinding (see printing)G
Hand binding or tooling
StoreF
Bottling works, for all beveragesG
Bowling alleysLimited as to number of lanesI
UnlimitedI
BreweriesG
Brick manufactureJ
Brush or broom manufactureG
Building materials salesopen or enclosed, limited as to lot areaF
Yards, for sales, storage, or handling, open or enclosed, unlimited as to lot area except in the case of lumber yardsF
Bungalow(See residential)A
BusinessOfficesB1
Research and testing laboratoriesB2
Essential servicesB3
Bus stationsWith less than 10 berthsK (bus area) and I (passenger area)
With 10 or more berths
MIXED (as per detail requirement including K and I)
Bus stopssee Bus stations
Business machinesManufactureG
Small, repair shopsF
Stores, sales, or rentals..F
Business schools or collegesB
Buying house (garments)storage restricted to sampleE
C
CaféSix persons or lessNon-separated use to main Occupancy
More than six persons (see mercantile)
F
CafeteriaWith commercial kitchenMIXED (G and I)
Without commercial kitchenI
Camera and photo equipmentManufactureG
Camps, overnight or outdoor dayMIXED (A, I and other depending on the nature of use)
Candy storesF
Canneries, including food productsJ
CanteenWith or without cooking facilityI
Canvas or canvas products manufactureG2
Cargo terminalcontaining low fire-risk materialsH
containing moderate fire-risk materialsH
J
containing high fire-risk materials
Carnivals, temporaryI5
Carpentry shopsG
CarpetCleaning establishments...J or G depending on the nature of materials involved
Manufacture
G
Carpet, rug, linoleum or other floor covering stores UnlimitedF
CarportRoofed wall less shelter for carK or H depending on the nature of use
Automated mechanical parkingK or H depending on the nature of use
Catering establishmentsCommercial kitchenG
OfficeE
Storage, open or enclosedH
Storage for temporary structure's fabrication materialJ
Cattle shed, stablesH
Cement manufactureG2
CemeteriesH
Ceramic productsManufactureG or J based on nature of material used
Display and sales
F
Chamber, doctors' or dentists', (outpatient only)50 or less occupantsE
above 50 occupantsD
Charcoal manufactureG
ChemicalsCompounding or packagingG or J depending on nature of materials involved
Manufacture
G or J depending on nature of materials involved
Child care homeC
Child care institutionC
Children's amusement parksSmallI
Medium sizeI
Large sizeI
Unlimited as to sizeI
Churches, with fixed pews(See Assembly with fixed seats)I
Cigar storesF
Cinema hall(See Assembly with fixed seats)I
Cineplex(See Assembly with fixed seats)I
Circuses, temporary(See Assembly)I
Class roomSchool, college or universityB
Clay manufactureG
Clay pitsNot applicable
Cleaning or cleaning and dyeing establishments(See dry cleaning)....
ClinicsWith inpatientD
Only outpatient, limited to quantity (see chambers, doctors' or dentists')
D
Only outpatient, unlimited
With diagnostic facilities (see diagnostic facilities)
E
Government community clinic
Coaching centre(See educational facilities)B
Cold storageH
Composite textile millG or J depending on nature of material and process used
Cottage industriesSmall, fifty or less workers (see industrial facilities)G1
G1 or G2 depending on the nature of material and process used
Large, more than fifty workers… (see industrial facilities)
ClockManufactureG
Stores or repair shopsF
ClothingAccessory storesF
Custom manufacture or altering for retailF
G or J depending on nature of the material involved
Manufacture
Rental establishments
F
Store, Limited as to floor areaF
Store, UnlimitedF
Clubs Non-commercial (members only)Including accommodationMIXED (A and I)
Night-clubI
All types except those with outdoor swimming pools
Clubs, for public useExcluding accommodationI
Including accommodationMIXED (I and A or other occupancies depending upon nature of use)
Clubs, SportingMIXED (I and A or other occupancies depending upon nature of use)
CoalProducts manufactureJ
Sales, open or enclosed, Limited as to plot areaJ
J
Unlimited (see coal storage)
Storage, open or enclosedJ
Coin storesF
Condensed and powdered milkManufactureJ
Coke productsManufactureJ
Colleges or universitiesSee educational facilitiesB
Colony, government or non-governmentMIXED (A and other occupancies depending on use)
Commercial building(see business and/or mercantile)
Commercial parking garages or plots(See garages)K
Community centersWith commercial kitchenMIXED (G and I)
Without commercial kitchenI
Concrete batchingG
Concrete products manufactureG
Construction machineryManufacture, including repairsG
Container terminalH or J (According to the hazard classification regulation of the port authority)
Contractors' establishmentsElectrical, glazing, heating, painting, paper hanging, plumbing, roofing, or ventilatingF
Not applicable
Contractors' yards
Convalescent homes(See nursing homes)
ConventsMIXED (A, B and I)
Cork productsManufactureG
Cosmetics or toiletriesManufacture..J
Costume rental establishmentsF
Cottage, tourist(See residential)A5
Cotton ginning or cotton wadding or liner manufactureJ
Court housesI
Crate manufactureG or J depending on the material and process involved
CrematoriumsAnimals.J
Human.MIXED (J and I)
Cultural centerMixed (depending on detail requirement)
D
Dance hallsPublicI
Dance SchoolA
Dance studios(see studios)
Day camps, outdoorI
Day care CentreWith six or less childrenNon-separated use to Residential Occupancy
More than six children
C
Decorator's establishmentOfficeE
Storage, separatedH or J depending upon the material involved
Defense Buildings, for critical national defense capabilitiesNot Applicable
Delicatessen stores(See food stores)F
DentalInstruments manufactureG
Laboratories (See laboratories, medical or dental)
Department storesnot exceeding 300 m²F1
more than 300 m²F2
Diagnostic facilities, medicalOutpatients onlyD
Diaper supply establishmentsH
Disinfectants manufactureG
DispensariesAttached to hospitalL
See drug storeF
DormitoriesUniversities or colleges (above 12 grade)A
Schools (12 grade or below)C
Drafting instrumentsManufactureG
Dressmaking shops, customF
Drinking places, non- alcoholic(See cafe)
Drive-in theatersI
Drug storesF
Dry cleaning or clothes pressing establishmentsLimited as to floor area, solvents and machine capacityG or J depending on the process and quantity of material used
Dry cleaning or cleaning and dyeing establishmentsWithout restrictionsG or J depending on the process and quantity of material used
Dry Cleaning, using other than flammable liquids in cleaning or dyeing operationsG
Dry goods storesLimited as to floor areaF
UnlimitedF
DumpsNot applicable
Dyeing facilities/ industriesJ
E
Eating or drinking placesWith restrictions on entertainment (see Assembly)I
I
Without restrictions on entertainment or dancing but limited to location in hotels (see Assembly)
I
Without restrictions (See assembly)
Eco park structuresMIXED (depending upon the nature of use)
Educational facilitiesUp to higher secondary levelB1
Training and above-higher-secondary educationB2
B3
Pre-school facilities
ElectricPower or steam generating plantsG
Substations, Public transit or railroadG
Substations, as part of public distribution systemG
L
Substations, low to medium voltage step down, at consumers' end
Electrical ApplianceManufactureG or J depending upon the process or material to be used
Stores (including television, radio, phonograph or household appliances)
F
Contractors (See contractors' establishments)
G
Equipment assembly, not including electrical machinery
G
Supplies, manufacturing
Electronics manufacturingJ
Electrolysis worksJ
Electrotyping or stereotypingLimited to quantityF
Unlimited (see printing)G
Embassy or High- commission or ConsulateMIXED (depending on detail requirement)
Engineincluding rebuilding or reconditioningJ
Engraving or photo- engravingLimited to quantityF
Unlimited (see printing)G
Excelsior manufactureJ
Exhibition hallSee assemblyI
ExterminatorsSee pest controlF
F
Fabric storesF
FactoryG or J (depending on process and material involved)
Fairs, temporaryMIXED (I and F)
FeathersBulk processing, washing, curing, or dyeingJ
J
Products manufacture, except washing , curing or dyeing
FeltBulk processing, washing, curing, or dyeingG
G
Products manufacture, except washing, curing or dyeing
Fertilizer manufactureJ
Field hospital, temporaryWith provision for ambulance access (to parks and play grounds)E
Filling stations(See refueling station)B
Film, photographicManufactureG
Fire StationsE
Fish products, packing or processingG
Fishing tackle or equipment rental or salesF
Flats(see residential)A
In walkup buildingsA
In high risesA
in housing complexMIXED (A and other occupancies)
Florist shopsF
FoodProducts processing, except meat slaughtering or preparation of fish for packingG
F
Stores, including supermarkets, grocery stores, meat markets, or delicatessen stores
FoundriesFerrous or non-ferrousG or J (depending on process and material involved)
Fraternity houses(See colleges or universities)
Freight depotSee storage and hazardous buildingsH and/or J
Frozen food lockersJ
Fuel briquettes manufactureG
Fuel sales, open or enclosedLimited up to exempted quantityF
Unlimited, See coal storage or petroleum storageJ
Funeral establishmentsI
Fungicides manufactureG
FurGoods manufacture, not including tanning or dyeingG
J
Tanning, curing, finishing, or dyeing
FurnitureCustom shop, floor area of 100 m² or lessF
G
Custom shop, floor area over 100 m²
ManufactureJ or G depending upon nature of materials involved
Store, Limited as to floor area
F
Store, UnlimitedF
Furriers shops, customF
Freight depotH or J depending on the nature of material involved
G
GaragesParking garageK1
Private garageK2
Repair garage and show-roomsK3
Garbage incineration or reductionG
Garden shedM
Garden supply storesF
Gardens, truck(See agriculture)
Garments industriesG
Gas, fuelManufactureJ
Distribution regulatory system (DRS)G
Gas manufacture forMedical purposeJ
Hot-works (welding)J
Gasoline service stations(See refueling stations)
Gelatin manufactureG
Generating plants, electric or steamG
Gift storesF
GlassCutting shopsF
ManufactureG
Products manufacture from previously manufactured glassG
Glazing contractor's establishment(See contractors' establishments)F
Glue manufactureG
GodownSee storage buildings
GolfCoursesNot applicable
Courses, miniatureI
Driving rangesI
GrainMilling or processingJ
StorageJ
Graphite or graphite productsManufactureG
Gravel pitsNot applicable
Grocery storesF
Group homesSegregation of occupants on the basis of age group and disabilities (See institutional)C
Gypsum production industryJ
GymnasiumsLess than 300 occupantsI
300 or more occupantsI
Commercial without spectator gallery (max 50 occupants)
H
HairBulk processing, washing, curing, or dyeingG
G
Products manufacture (except washing, curing, or dyeing)
G
Products manufacture, custom
Hall, for incidental show (picture, drama, theatre)(See assembly)I
HardwareManufactureG
StoresF
Bodies manufactureG
Repair shopsF
Hazardous buildingsExplosion-hazard buildingJ1
Chemical-hazard buildingJ2
Biological-hazard buildingJ3
Nuclear-hazard buildingJ4
Health centersWith inpatientD
Without inpatient (not more than 50 occupants)E
E or D (depending upon the facilities)
Government operated health centers
Healthcare facilitiesNormal medical facilitiesD1
Emergency medical facilitiesD2
Health clubI
Heating contractor's establishment(See contractors' establishments)
Heat, ventilation and air-conditioning equipment showroomsWithout repair facilitiesF
HeliportsG
Hemp products manufactureG
High CommissionSee embassy
Home for careof the old and infirm (see institution)
of mentally disabled (see institution)
Home officeNot more than 6 occupantsNon-separated use of Occupancy A
Hosiery manufactureG
Hospital, except animal hospitalAs part of disaster preparedness programD
D
Casualty unit
Emergency unitD
Non-profit or voluntary, and related facilitiesD
D
Proprietary and related facilities
HostelsFor adultsA
For childrenC
HotelsTransientA
Apartment hotelA
Starred hotelMIXED
HouseholdAppliance repair shopsF
Appliance stores (See appliances television, radio, phonograph, or household appliance stores)F
Housing, complex multi-storiedMIXED (see appendix)
Housing, clusterMIXED (see appendix)
Housing, low-incomeMIXED (see appendix)
Housing, minimum standardMIXED (see appendix)
Housing, rehabilitationMIXED (see appendix)
I
Ice cream storesF
IceManufacture, dry or naturalG or J (depending on the process or material used)
Sales, open or enclosed Limited as to lot area
F
F
Unlimited
Incineration or reduction of garbage, offal, or dead animalsG
Indoor facility, for amusement parkI
Industrial buildingsLow-hazard IndustriesG1
Moderate-hazard IndustriesG2
InfirmariesC
Ink or inked ribbon manufactureG or J depending on nature of materials involved
InnsSee residentialA
Insecticides manufactureG or J depending on nature of materials involved
InstitutionFor care of childrenC1
Custodial, for physically capable adultsC2
C3
Custodial, for physically incapable adults
C4
Penal or mental, for children
Penal or mental, for adultsC5
Institutions, philanthropic or non- profitWith sleeping accommodationsA
Without sleeping accommodations
Interior decorating establishmentsLimited as to floor area for processing, servicing, or repairsF
F
Unlimited, see furniture, textiles or upholstering
Irradiation plantJ
J
Jailsee prisons
JewelryManufactureG
CostumeG
From precious metalsG
ShopsF
Junk YardsNot applicable
Jute products manufactureG or J (depending on quantity or process)
Juvenile correctional centerFor children (see assembly)
K
KennelsH
KindergartenSee educational facilitiesB
Knitwear industriesG2
L
LaboratoriesMedical or dental, for research or testing, with limitations on objectionable effectsE
(G or J) and H depending on process or material used in compliance with safety standards
Research, experimental, or testing, unlimited
Radiological laboratory, see radiological facilities
G (in compliance with safety standards)
Pathological laboratory
Microbiological laboratory, for diagnostic facilityG or J depending on process or material used in compliance with safety standards
Microbiological laboratory, for research
G or J depending on process or material used in compliance with safety standards
Microbiological laboratory, for academic facilityG or J depending on process or material used in compliance with safety standards
Lampblack manufactureG
Laundries, with no limitations on type of operationG
Laundry establishments, hand or automatic self- serviceG
Lavatory, publicsee public toilet
LeatherTanning, curing, finishing or dyeingJ
Goods storesF
Products manufactureG
LibrariesReading area (see assembly)I
Stack area (see storage)H
Reading and stack area combinedMIXED (I and H)
Lillah boardingFor children (see institutional)C
For adults (see residential)A
Linen supply establishments
LinoleumManufactureJ
Stores (See carpet stores)
Liquor stores, packageF
LivestockStorage, more than six castlesH
Slaughtering or preparation for packingG
Loan officesE
Locksmith shopsF
LodgingSee residentialA
LuggageManufactureG
StoresF
LumberProcessing or woodwork, bulkG
Sales, Limited as to lot areaG
Sales, UnlimitedG
Yard, Limited as to lot areaG
Yard, UnlimitedG
M
MachineShops including tool, die or pattern makingG
Tools manufactureG
MachineryManufacture or repair, HeavyG or J depending on material and process
Miscellaneous or electrical equipment
G or J depending on material and process
Rental or sales establishments
F
Repair shopsF
Machines, business(See business machines)
Madrasa(See institution)
Manure storageH
MarketsRetail, including meat (See mercantile)F
Wholesale, produce or meat (See mercantile)F
MasseursF
Matches manufactureJ
Mattress manufacture, rebuilding or renovatingJ
MeatMarkets, Retail (See food stores)F
Markets, WholesaleF
Slaughtering or preparation for packingG
MedicalAppliances, Custom manufactureG
Appliances, ManufactureG
StoresF
Instruments, manufactureG
Laboratories (See laboratories, medical)
E
Offices or group medical centers, Limited as to location within building
E
Offices or group medical centers, Unlimited
Meeting hallsSee AssemblyI
Mess houses(See residential)
Metal Fabrication industryJ
Metal Assembly industryJ
Metals manufactureAlloys or foil, miscellaneousG
Casting or foundry products, heavyG
Finishing, plating, grinding, sharpening, polishing, cleaning, rust proofing, heat treatment, or similar processesG
Ores reduction or refiningG
Products treatment or processingG
Reduction, refining, smelting, or alloyingG
G
Stamping or extrusion
Treatment or processingG
Mental institutionWithout detention facilitiesD
Mental hospitals(See institution)C
MercantileSmall shops and marketsF1
Large shops and marketsF2
Refueling stationF3
Mill(See industrial and/ or hazardous buildings)G or J (depending on material or process)
Mill works, and woodworking, wood distillation and particle boards manufacturingJ
Millinery shopsF
Mining machinery manufactureIncluding repairsG
Mirror silvering shopsG
Miscellaneous buildingsSpecial structuresM1
Fences, tanks and towersM2
MonasteriesMIXED
MonumentSales establishments, with incidental processing to orderF
Works, with no limitations on processingG
Mosque(See assembly)I
Motels(See residential)A
Motion picture production and filming facilitiesMIXED (G and other Occupancies as required)
MotorcyclesManufactureG
Repairs, bodyG
Repairs, except body repairsG
Sales open or enclosedF
Showrooms, with no repair services (See garage)K
Motor freight stationsSee truck terminals
Motor vehiclesDead storageH
Moving or storage offices, Limited as to storageK
K
Unlimited
Movie theatreSee assemblyI
MuseumsSee assemblyI
Music storesF
Music studiosSee studios
Musical instrumentsManufacture, Excluding pianos and organsG1
G2
Including pianos and organs…
Repair shops…G1
N
Newspaper publishingPrintingMIXED (G and E)
G
OfficeE
Newsstands, open or closedF
Novelty products manufactureG
Novitiates…See institutionA
Nuclear medicine facilitiessee radiological facilities
Nuclear plantJ
NurseriesSee agriculture
Nursing homesPhilanthropic or non-profitC or D depending on the type of occupants and nature of use
Private
C or D depending on the type of occupants and nature of use
Nursery schoolsSee pre-schoolB
O
Oakum products manufactureG
Office equipment or machinery repair shopsF
Office or business machine storessales or rentalF
OfficesGeneralE
Business, professional or Governmental (see business occupancy)E
E
Dental, medical, or osteopathic (See medical offices)
E
Wholesale, with storage restricted to samples (see business occupancy)
Offices, smallArchitect's/engineer's/ consultant's (Limited to six occupants)Non-separated use of Occupancy A
Architect's/engineer's/consultant's ( more than six occupants)E
Oil cloth manufactureJ
Oil sales, open and enclosedLimited as to lot areaF
Unlimited (See petroleum or petroleum products storage)J
Old homeSee institutionC
OpticalEquipment manufactureG
Goods manufactureG
OrphanageSee institutionC
Optician or optometrist establishmentsF
OrthopedicAppliances, Custom manufactureG
ManufactureG
StoresF
Instruments, manufactureG
Osteopathic offices(See medical offices)
P
Packing or crating establishmentsG2
Packing materials manufactureG2
PagodaSee Prayer hall
PaintManufactureJ
Stores, limited to quantityF
Stores, unlimitedH
Painting contractors(See contractors' establishments)
PaperMills (See wood pulp or fiber)G
Products manufactureG
Stock companiesH
Paper-hanging contractors(See contractors' establishments)
Parish housesA
Parks, public or privateWith provision for emergency vehicle access as part of disaster preparedness programNot applicable
Park structuresM
Parking garages, publicSee garage, parkingK
Parking lots, publicSee garage, parkingK
Passenger stations and terminalsSmall, passenger stationMIXED (depending on nature of use)
Large, passenger station or terminal
MIXED (depending on nature of use)
Passenger and freight terminal
MIXED (depending on nature of use)
Peat storageH
Perfumed or perfumed soapscompounding only, not including soap manufactureJ
Pest controlExempted quantity onlyF
Pet shopsF
Petrol pumpSee refueling stationF
Petroleum or petroleum productsRefiningJ
Storage and handlingJ
Pharmaceutical products manufactureG or J depending on nature of materials used
Philanthropic, religious or non-profit activitiesMIXED (depending on nature of use)
PhonographRepair shopsF
Stores (See appliances)F
Photocopying and book bindingBinding limited in quantityF
PhotographicDeveloping or printing establishment, RetailF
H
Developing or printing establishment, Wholesale, Limited as to floor area
H
Developing or printing establishment, Wholesale, Unlimited
J
Equipment, Manufacture (film)
Equipment, Manufacture (except film)G
StoresF
StudiosF
Supply stores (limited to exempted quantity)F
Photostatting establishmentsF
Physical culture establishmentsI
Picture framing storesF
Plants, IndustrialG
Plants, RefrigerationG
PlasticsProducts, manufactureJ
Raw, manufactureJ
Plate making(See printing)
PlaygroundsWith provision for emergency vehicle access as part of disaster preparedness programI
Plots, parking(See parking lots, public)
PlumbingContractors' establishmentsF
Equipment manufacturer (See tools or hardware manufacturing)
F
Showrooms, without repair facilities
Police StationsE
Pool hallsI
Porcelain products manufactureG
Post officesE
PoultryStorage (live)H
Killing establishments, for retail sales on the same zoning lot onlyG
G
Packing or slaughtering
Power plantG
Power stationsAs part of national grid power distribution systemE
L
At consumer's end
Prayer hallSee assemblyI
Precision instruments manufactureOptical equipment, clocks, or similar productsG
G
Medical, dental, or drafting instruments, optical goods, or similar products
Pre-school facilitiesSee educational
Press club, for journalistI
Press, printingSee printing
Primary schoolsSee educational
PrintingCustomG
Limited as to floor areaG
UnlimitedG
Printing, publishing, dyeing and printing industriesJ
PrisonsSee jailC
Produce or meat markets, wholesaleF
Psychiatric sanatoriaWith detention facilities (see institution)
Public auction roomsMIXED (F and/or I)
Public transit yardsNot applicable
PublishingWith printingG
Without printingE
Pumping stationsWater or sewage (for city supply system)G
U
Dedicated to consumer
Q
Quarter, StaffGovernment or non-governmentA or Mixed (See appendix)
R
RacetracksI
RadioAppliance repair shopsF
StoresF
Studios, with less than six occupantsNon-separated use to main Occupancy
Studios, without transmission tower
E
Studios, with transmission tower (see radio station)
M
Towers, non-accessory
Radio stationMixed (depending on the type of use)
Radiological facilities, medicalIn compliance with the standard of atomic energy commissionD
Radioactive waste disposal servicesJ
RailroadEquipment manufacture, including railroad cars or locomotivesG or J depending on the material and hot-work used
Passenger stations
I
Right-of-wayNot applicable
Substations
G
Small or medium size
LargeG
Railroads, including rights-of-way, freight terminals, yards or appurtenances, or facilities or services used or required in railroad operations, but not including passenger stationsNot applicable
Rail stationMixed (depending on the type of use)
Record storesF
Recreation centers, non-commercialI
Recreation piersSee assemblyI
Recreational vehicles manufacturingJ
RectoriesA
Reducing salonsI
ReformatoriesSee institutional facilities
Refreshments stand, drive-inI
Refrigerating plantsG
Refueling stationPetroleum product storage within exempted quantityE
Refuse incineratorsJ
Religious or church art goods manufactureG
Research establishmentdealing with non-hazard or low hazard materials onlyE
ResidencesSingle-family detachedA
One-family semi-detached or two- family detached or semi-detachedA
A
Boarding or rooming houses
Rest homes (See nursing homes)
ResidentialSingle family dwellingA1
Two family dwellingA2
Flats or apartmentsA3
Mess, boarding house, dormitories and hostelsA4
A5
Hotels and lodging houses
Rest Houses
RestaurantDining areaI
Performing area, limitedI
Kitchen and storageL
Reviewing standI
Riding academies, open or enclosedE and H
Roofing contractors' establishmentsF
Rooming housesSee residentialA
RubberProcessing or manufacture, natural or syntheticJ
J
Products manufacture (excluding all natural or synthetic rubber processing)
Rug stores(See carpet stores)
S
Sail-making establishmentsF
Salvage storageH
Sand pitsNot applicable
Saloon, hair dressingF
SanatoriumsWith detention facilities (see institution)C
Without detention facilitiesD
SawmillsG
Scenery constructionG
School (see educational)Dormitories, for childrenC
Nursery, kindergarten, elementary or secondary schoolsB
B
Trade or other schools for adults, limited as to objectionable effects
B
Trade schools for adults, unlimited
For physically challenged, without accommodationB
For mentally challenged, without accommodationB
Scrap metal, paper and rag storageH
Secondary schoolSee educationalB
Seed storesF
Seminar hallsFor 50 or more occupants, See assemblyI
SeminariesB
Settlement houses(see housing)MIXED (A and other Occupancy depending on the nature of use
SewageDisposal plantsG
Pumping stationsG
Sewing machine stores, selling household machines onlyF
Ship chandlers, candle shopsF
Ship or boat building or repair yardsFor ships 200 ft. in length or overG
Shipping, waterfrontNot applicable
ShoesManufactureG or J depending on the process and material involved
Repair shops
F
StoresF
Shopssee definitionF or G (depending on the process and material involved)
Shop-housemixed occupancy (A and F) or (A, F and G)
Sign painting shopsLimited as to floor areaG
UnlimitedG
Silk processing and spinningJ
Silo, for storage of grainH
Silver plating shops, customG
Silverware manufacture, plate or sterlingG
Sisal products manufactureJ
Skating rinks, rollerIndoorI
OutdoorI
Slag pilesNot applicable
Slaughtering of animals or poultryG
Soap or detergentsManufacture, including fat renderingJ
Packaging onlyG
Soldering shopsG
Solvent extractingJ
Sorority houses(See hostel)A
Sports centreI
Sporting equipment manufacture.G
Sporting goods storesF
Stable for horsesH
StadiumsIndoor or outdoor, with access for emergency vehicle as part of disaster preparedness programI
Staff quartersee quarter, staff
Stamp storesF
StationRail, bus, air and water wayMIXED (I and other Occupancy depending on the nature of use
Stationary storesF
Statuary, mannequins, figurines, religious or church art goods manufacture, excluding foundry operationsG
Steel productsMiscellaneous fabrication or assembly (without hot-work)G
J
Structural products manufacture
Stock yards or slaughtering of animals or poultryG
Stone processing or stone productsG
Storage buildingsLow-fire-risk storageH1
Moderate-fire-risk storageH2
Storage facilitiesWholesale (see storage buildings)H
Offices, limited to quantityNon-separated use
For cotton/jute/ paper/textileJ
StoresSee definitionF
Students' halls of residenceFor childrenC
For adultsA
StudiosMusic, dancing, or theatricalI
Radio (see radio studio)
MIXED (I, E or G)
Television, with spectator
Television, without spectatorMIXED (depending on nature of material and process involved)
SugarProduction and RefiningJ
Super marketSee mercantileF
Swimming poolsCommercialI
Non-Commercial (See clubs)I
T
Table tennis hallsSee assemblyI
Tailor shops, customF
Tanning (See leather or fur)J
Tapestries manufactureG
Tar products manufactureG
Taxidermist shopsF
Telegraph officesE
Telephone exchanges or other communications equipment structuresE
TelevisionRepair shopsF
Stores (See appliances)F
Studios (see television studios)
M
Towers, non-accessory
Television stationSee businessMIXED (E3 with other Occupancies according to detail requirement)
TempleSee prayer hall
Tennis courts, indoorI
Terminal facilities at river crossings for access to electric, gas, or steam linesG
Test laboratoryinvolving low hazard materialE
TextilesBleaching (see industrial)G
Products manufacture (see industrial)G
Spinning, weaving, manufacturing, dyeing, printing, knit goods, yarn, thread, or cordage (see industrial)G
Textile industries and jute millsincluding canvas, cotton cloth, bagging burlap, carpet and rags (see industrial)J
TheaterSee assemblyI
Theaters, drive-in(See studios)
Theatrical studioswithout spectatorG
TileManufactureG
Tire sales establishmentsIncluding installation services, Limited to quantityF
J
Including installation services, unlimited quantity
TobaccoCuring or manufacture, or tobacco products manufactureJ
F
Stores (retail)
Toilet, publicL
Toiletries manufactureG or J depending on the material and process involved
Tool or hardware manufactureSee industriesG
Topsoil storageSee storageH
Tourist cabinsSee residentialA
Towel supply establishmentsF
ToysManufactureG
StoresF
Trade or other schools for adultsLimited as to objectionable effects (see educational)B
B
Unlimited (see educational)
Trade expositionsLimited as to rated capacityI
UnlimitedI
Trailer, truck, busManufacture, including partsG or J depending on the material and process involved
Repairs, body
G or J depending on the material and process involved
Sales open or enclosed
F
Showrooms, with no repair servicesF
Training centerlecture based, limited to quantity (see educational facilities)E1 or B2
B2
vocational or demonstrative (see educational facilities)
Transit substationsSmall or medium sizeG
LargeG
Transport terminalSmall or medium sizeMIXED depending on nature of use
Large
MIXED depending on nature of use
Travel agency(see business)E
Travel bureaus(see business)E
TruckManufacture (including parts) or engine rebuildingG or J depending on the material and process involved
Repairs, body
G
Repairs, except body repairsG
Sales open or enclosedF
Showrooms, with no repair servicesF
Trucking terminals or motor freight stations, Limited as to lot areaK1
K1
Trucking terminals or motor freight stations, Unlimited
Tutorial homesMore than six occupants (see educational)B
Turpentine manufactureJ
Typewriter storesF
Typewriter or other small business machine repair shopsF
Typography(See printing)
U
UmbrellasManufactureG
Repair shopsF
UniversitySee educational facilitiesB2
UpholsteryManufacturingJ
Bulk, including shops not dealing directly with consumersJ
F
Shops dealing directly with consumers, retail
UtilityL
V
Variety storesLimited as to floor areaF
UnlimitedF
Varnish manufactureJ
VehiclesDead storage of motorH
Manufacture, children'sG
Storage, commercial or public utility, open or enclosedK
Venetian blind, window shade, or awningCustom shops, limited as to floor areaF
Manufacture, with no limitation on production or on floor areaJ or G depending upon nature of materials involved
Ventilating contractors(See contractors' establishments)F
Ventilating equipment showroomsWithout repair facilitiesF
Video games shopF
Vihara, Buddhistwith occasional or regular assemblymixed use
W
Wallpaper storesLimited to quantityH
WarehousesH or J (depending on the nature of material stored)
Watch or clock stores or repair shopsF
Watch makingG
Waterfront shippingNot applicable
Water pumping stationsAt distributor's endG
At consumer's endL
Water tank towerM
Wax products manufactureG
Weaving, handUp to six hand-weaving machinesNon- separated use to main Occupancy
More than six hand-weaving machines
G
Wedding chapelsSee assemblyI
Welding shopsArc welding onlyG
Gas welding within exempted quantityG or J depending upon the quantity of material and process
Welfare centers
Wholesale establishmentsH or J depending upon the nature of material
Wholesale offices or showrooms, with storage restricted to samplesE
Window manufactureG
Window shadesCustom shops, limited as to floor areaF
Manufacture, without limitation on production or on floor areaG
WoodBulk processing or woodworkingG
DistillationG
Products manufactureG
Pulp or fibre, reduction or processing, including paper mill operationsG
F
Sales, open or enclosed, Limited as to lot area
F
Unlimited (See lumber yards)
Woodworking shops, customJ or G depending upon nature of materials involved
Wool scouring or pullingG
WorkshopsWith hot-worksJ
Without hot-worksG
X
X-ray facilitiesSee radiological facilities
Y
YardNot applicable
Yard, shipSee ship or boat building or repair yards
Yarn, manufacturingG or J depending on the quantity (see Table 3.2.5)
Z
Zoo structuresM
** The occupancy determined throughclassification for any project, not included the following process:in this list, shall be
shall be compared with categories and find the most similar
i. The functional the Occupancy descriptions to Occupancy,requirements of the unidentified occupancy use type, classification, sub-classification match with the given occupancies to
to determine the Occupancy, the project constituted as per directives of Part 2 the Occupancy, andwill be referred to the Chapter 2. The Board of
ii. If process (i) fails Board of Appeal Appeal shall determine
explanatory material of any future projects of referred to the Board of
iii. The decision of Board this Code and shall similar nature this Appeal again.of Appeal shall be considered as an be added as addendum to this Code. For addendum will suffice and need not be

PART III

Chapter 3: Classification of Building Construction Types Based on Fire Resistance

3.1 General

3.1.1 Classification by Type of Construction

For the purpose of this Code, every room or space of a building or a building itself hereafter altered or erected shall be classified in one specific type of construction as grouped as follows:

GROUP I: Noncombustible, subdivision

Type I-A: 4 hour fire protected

Type I-B: 3 hour fire protected

Type I-C: 2 hour fire protected

Type I-D: 1 hour fire protected

Type I-E: Unprotected

GROUP II: Combustible subdivision

Type II-A: Heavy timber

Type II-B: Protected wood joist

Type II-C: Unprotected wood joist

Type II-D: Protected wood frame

Type II-E: Unprotected wood frame

The fire resistance ratings of various types of construction for structural and non-structural members are specified in Tables 3.3.1 (a) and (b). For hazardous Occupancies involving an exceptionally high degree of fire risk or an exceptionally high concentration of combustible or flammable content, the Authority may increase the requirement of Table 3.3.1 (a).

Buildings having a height of more than 33 m shall be constructed with non-combustible materials.

The fire resistance ratings of various building components shall conform to ASTM standards.

No building or portion thereof shall be designated a given construction type unless it fully conforms to the minimum requirements for that Construction type.

When a type of construction is utilized which is superior than the type of construction required by this Code, there shall be no requirement to upgrade the rest of the construction to comply to that higher type of construction and the designated construction type shall be that of the lesser classification, unless all of the requirements for the higher classification are met.

3.1.2 Group I: Non-Combustible Construction

Buildings or portion thereof in Non-combustible Construction Group I are those in which the walls, exit-ways, shafts, structural members, floors, and roofs are constructed of non-combustible materials and assemblies having fire-resistance ratings specified in Table 3.3.1 (a). The Non-combustible group consists of Construction Type I-A, I-B, I-C, I-D and I-E.

3.1.2.1 Construction Type I-A

This construction type includes buildings in which the bearing walls and other major structural elements are generally of four-hour-fire-resistance rating.

3.1.2.2 Construction Type I-B

This construction type includes buildings in which the bearing walls and other major structural elements are generally of three-hour-fire-resistance rating.

3.1.2.3 Construction Type I-C

This construction type includes buildings in which the bearing walls and other major structural elements are generally of two-hour-fire-resistance rating.

3.1.2.4 Construction Type I-D

This construction type includes buildings in which the bearing walls and other major structural elements are generally of one-hour-fire-resistance rating.

3.1.2.5 Construction Type I-E

This construction type includes buildings in which the bearing walls and other major structural elements generally have no fire-resistance rating.

3.1.3 Group II: Combustible Construction

Buildings or portion thereof in Combustible Construction Group II are those in which the walls, exit-ways, shafts, structural members, floors, and roofs are constructed wholly or partly of combustible materials having fire-resistance ratings specified in Table 3.3.1 (b). The Non-combustible group consists of Construction Type II-A, II-B, II-C, II-D and II-E.

3.1.3.1 Construction Type II-A

This Construction type includes heavy timber construction in which fire-resistance is attained by –

(a)Limiting the minimum sizes of wood structural members and the minimum thickness and composition of wood floors and roofs;

(b)Avoiding concealed spaces under floors and roofs or by providing fire-stopping protection for these spaces; and

(c)Using fastening, construction details, and adhesives for structural members as required by this Chapter and Part 4.

(d)The minimum dimensions for framing members shall be prescribed in this Chapter and Part 4, except that members are protected to provide a fire-resistance rating of at least one hour need not comply with this requirement.

3.1.3.2 Construction Type II-B

This Construction type includes buildings and portion thereof in which

(a)Exterior walls, fire walls, exit-ways, and shaft enclosures are of non-combustible materials having the required fire-resistance ratings; and

(b)The floors, roofs and interior framing are wholly or partly of wood of smaller dimensions than required for type II-A construction, or are of other combustible or non-combustible materials, having the required fire-resistance rating.

Table 3.3.1 (a): Fire Rating for Construction Group I: Non-Combustible

Exterior wall with Fire Separation Distance ofConstruction Element
Exterior Wall
TYPE -I-ATYPE -I-BTYPE -I-CTYPE -I-DTYPE -I-E
Ratings in HoursExterior Openinga,bRatings in HoursExterior Openinga,bRatings in HoursExterior Openinga,bRatings in HoursExterior Openinga,bRatings in HoursExterior Openinga,b
0.9m or lessBearing4N.P3N.P2N.P2N.P2N.P
Non-bearingf22222
More than 0.9m but less than 4.5mBearing4as per provisions of this Code3as per provisions of this Code2as per provisions of this Code2as per provisions of this Code2as per provisions of this Code
Non-bearingf22222
4.5m or more but less than 9.0mBearing43210
Non-bearingf1½1½110
9.0m or moreBearing4N.L3N.L2N.L1N.L0N.L
Non-bearingf00000
Interior bearing walls and bearing partitions43210g,i
Enclosure of vertical exitse, exit passageways, hoistways and shafts22222
Fire divisions and fire barrier walls or partitions or ceiling slabSee Table 3.2.1 and provisions of this Code
Columnsk, girders, trusses (other than roof trusses) and framingSupporting one floor321½10g,i
Supporting more than one floorl43210g,i
Structural members supporting wallsStructural members shall have the same fire resistance rating of wall to be supported, but not less than rating required by the construction classification.
Floor construction including beams321½10g,i
Roof construction, including beams, trusses and framing including arches, domes, shells, cable supported roofs and roof decksh4.5m or less in height above floor to lowest member of ceiling31½1i1i0g,i
4.5m to 6m in height above floor to lowest member of ceiling2c,i or 1d,i1½c,i or 1d,i1i1i0g,i
6m or more in height above floor to lowest member of ceiling2c,i or 0d,g,i1½c,i or 1d,g,i1c,i or 0d,g,i1c,i or 0d,g,i0g,i
Shafts (other than exits) and elevator hoistways22222
Fire separation wall and party wall42222
Access corridor leading to fire exits11111
Non-combustible Material;   N.P Not Permitted;   N.L No Limit

Table 3.3.1 (b): Fire Rating for Construction Group II: Combustible

Exterior wall with Fire Separation Distance ofConstruction Element
Exterior Wall
TYPE -II-ATYPE -II-BTYPE -II-CTYPE -II-DTYPE -II-E
Ratings in HoursExterior Openinga,bRatings in HoursExterior Openinga,bRatings in HoursExterior Openinga,bRatings in HoursExterior Openinga,bRatings in HoursExterior Openinga,b
0.9m or lessBearing2N.P2N.P2N.P2N.P2N.P
Non-bearingf22222
More than 0.9m but less than 4.5mBearing2as per provisions of this Code2as per provisions of this Code2as per provisions of this Code1as per provisions of this Code1as per provisions of this Code
Non-bearingf22211
4.5m or more but less than 9.0mBearing22210
Non-bearingf22210
9.0m or moreBearing1N.L1½N.L1½N.L1N.L0N.L
Non-bearingf00000
Interior bearing walls and bearing partitions21010
Enclosure of vertical exitse, exit passageways, hoistways and shafts221i1i1
Fire divisions and fire barrier walls or partitions or ceiling slabSee Table 3.2.1 and provisions of this Code
Columnsk, girders, trusses (other than roof trusses) and framingSupporting one flooras per provisions of this Code10 or 1j10
Supporting more than one floorlas per provisions of this Code10 or 1j10
Structural members supporting walls32½21½1
Floor construction including beamsas per provisions of this Code10 or 1j10
Roof construction, including beams, trusses and framing including arches, domes, shells, cable supported roofs and roof decksh4.5m or less in height above floor to lowest member of ceilingas per provisions of this Code3/403/40
4.5m to 6m in height above floor to lowest member of ceiling
6m or more in height above floor to lowest member of ceiling
Shafts (other than exits) and elevator hoistways22222
Fire separation wall and party wall42222
Access corridor leading to fire exits11111
Non-combustible Material;   N.P Not Permitted;   N.L No Limit

Notes:

a Requirements of protected exterior openings shall not apply to religious assembly. [Protected openings within an exterior separation of 0.9m or less are permitted for buildings classified in Occupancy Groups A provided, however said openings do not exceed in total area of 25% of the façade of the storey in which they are located. The openings however, may not be credited towards meeting any of the mandatory natural light and ventilation as per provisions of this Code. Protection of openings with an exterior separation of 0.9 m to 9 m shall not be required for A-1, A-2 and A-3 Occupancy groups] or to buildings classified in Occupancy groups J, G and H additional requirements for exterior walls and exterior wall openings as per provisions of this Code.

b Upon special application, the area development authorities may permit exterior wall openings to be constructed in excess of the permitted area established by this Table if such openings at the time of their construction are located at least 18m in a direct line from any neighboring building except as otherwise permitted in footnote f. Such additional openings may not however be credited toward meeting any of the mandatory natural light and ventilation requirements of Sec 1.19 Part 3 of this Code. If any neighboring building is later altered or constructed to come within the above distance limitation, the affected exterior openings shall immediately be closed with construction meeting the fire-resistance rating requirements for exterior wall construction of the building in which they are located.

c Applies to occupancy groups J, G and H

d Applies to occupancy groups J, G and H

e See Provisions of this Code for additional impact resistance requirements applicable to certain stair enclosures and for certain exceptions to stair enclosure requirements.

f When two or more buildings are constructed on the Plot and the combined floor area of the buildings does not exceed the limits established by this Code for any of the buildings, not fire-resistance rating shall be required for non-bearing portions of the exterior walls of those buildings facing each other, and there shall be no limitation on the permitted amount of exterior openings.

g Fire retardant treated wood complying with the requirements of this Code may be used.

h Tabulated ratings apply to buildings over one storey in height. In one storey building, roof construction may be of material having zero hour fire-resistance rating.

i Materials which are not non-combustible as defined in this Code may be used in nonbearing construction elements as per provisions for this Code.

1 Materials having a structural base of non-combustible materials as defined in this Code, and having a surface not over 3.2 mm thick which when tested in accordance with the provisions of this Code has a flame spread rating not higher than 50 (fifty).

2 Materials which when tested in accordance with the provisions of this Code have a surface flame spread rating not higher than twenty five without evidence of continued progressive combustion, and which are of such composition that surface which would be exposed by cutting through the material in any way would not have a flame spread ratings higher than twenty-five without evidence of continued progressive combustion.

j Applies to the construction of the street floor and all construction below the level of the street floor in building or spaces classified in occupancy group A-3 except where the space below the street floor does not exceed five feet in height.

k Columns supproting the roof of a one-story building shall have the same fire-resistance rating as required for a column supporting one floor in a building of the same construction class.

l Members supporting loads of not more than two floors or one floor and a roof need not have a fire-resistance rating greater than the floor construction fire-resistance requirement in buildings classified in occupancy groups B, C and A-3, not including unsprinklered spaces of other occupancies, and in fully sprinklered buildings in occupancy groups E and A-5.

3.1.3.3 Construction Type II-C

This Construction type includes buildings and portion thereof in which

(a)Exterior walls, fire walls, exit ways, and shaft enclosures are of non-combustible materials having the required fire-resistance ratings; and

(b)The floors, roofs and interior framing are wholly or partly of wood of smaller dimensions than required for type II-A construction, or are of other combustible or non-combustible materials, having no required fire-resistance rating.

3.1.3.4 Construction Type II-D

This Construction type includes buildings and portion thereof in which exterior walls, bearing walls, floors, roofs, and interior framings are generally of wood or other combustible materials having the required fire-resistance ratings.

3.1.3.5 Construction Type II-E

This Construction type includes buildings and portion thereof in which

(a)The exterior walls are generally of wood or other combustible materials having the required fire-resistance ratings, and

(b)In which the bearing walls, floors, roofs, and interior framing are of wood or other combustible materials, generally having no fire-resistance ratings.

3.1.4 Separated Occupancy and Construction

When two or more occupancies accommodated in a building, each such occupancy shall be separated according to the provisions specified in Sec 2.3 Chapter 2 Part 3 and Table 3.2.1.

When two or more types of construction used within a building, the entire building shall be subject to the most restrictive construction type and shall comply with FAR restrictions as per provisions of this Code.

However if the Occupancies within the different Types of Construction are completely separated by construction that meets the fire-resistance rating requirements for fire separation listed in Table 3.2.1 of Chapter 1 Part 3 then each Occupancy so separated may, for the purpose of this Code, be considered as separate building section.

3.1.4.1 Restriction for mixed construction

In buildings of mixed construction, no structural element shall be supported by construction having a lower fire-resistance rating than that required for the element being supported.

3.1.5 Fire Zones

The planning and development authority of the city, township, municipality or region where this Code is intended to be implemented shall divide the area under their jurisdiction into distinct fire zones. The basis for this zoning shall be the fire hazard inherent in the buildings and the degree of safety desired for the occupancy accommodated therein. The number of zones in an area shall depend on its size and the strategies undertaken for its development.

3.1.5.1 Fire Zone 1

The following occupancy groups shall comprise this zone:

Occupancy A: Residential Occupancy F: Mercantile Occupancy B: Educational Occupancy H: Livestock Storage Building Occupancy C: Institutional for Care Occupancy I: Assembly

Occupancy D: Health Care Occupancy K: K1 and K2 Parking

Occupancy E: Offices Occupancy M: Miscellaneous Buildings

3.1.5.2 Fire Zone 2

The following occupancy groups shall comprise this zone:

Occupancy G: Industrial Buildings

Occupancy H: Storage Buildings

Occupancy K: K3 Parking

3.1.5.3 Fire Zone 3

The only occupancy falling in this zone shall be Occupancy J, Hazardous Buildings.

3.1.5.4 Change in Fire Zone Boundaries

The demarcations of fire zones may be changed or new occupancies may be included in any fire zone through the same procedure as for promulgating new rules or ordinances or both.

3.1.5.5 Buildings on overlapping fire zones

Buildings falling on more than one fire zones shall be considered to be situated on the zone in which the major portion of the building falls. If a building is divided equally between more than one fire zones, it shall be considered as falling in the fire zone having more hazardous occupancy buildings.

3.1.5.6 Restrictions on temporary constructions

Permission may be granted by the Authority for temporary constructions only in fire zones 1 and 2 and not in fire zone 3. Such temporary constructions shall adhere to the conditions of the permission and shall be demolished and removed completely after the expiry of the duration of the permission unless it is extended by the Authority or a new permission is obtained.

3.1.6 Permissible Types of Construction for Various Occupancies

3.1.6.1 New buildings

Types of constructions permitted for various buildings on the basis of fire zones are specified in Table 3.2.4.

3.1.6.2 Existing buildings

Existing buildings in any fire zone need not comply with the provision of this Code for type of construction unless they are altered or in the opinion of the Authority they constitute a hazard to the safety to the occupants of the buildings or the adjacent properties.

3.1.7 Exterior Walls

The fire resistance rating of the exterior walls shall conform to the provisions set forth in Table 3.2.2 and Sec 3.2.3.

3.1.8 Basement Floor

Basement floor of a building shall be enclosed with a one hour fire resistive construction. Doors in such constructions shall be made of noncombustible materials.

3.1.9 Restricting Horizontal and Vertical Spread of Fire

Generally walls restrict horizontal movement and slabs restrict vertical movement of fire.

3.1.9.1 Interior or barrier or enclosure wall

Propagation of fire, smoke, gas or fume through the openings or shafts or penetrations of fire resistive floors and walls shall be restricted by sealing with an approved material which shall have a fire resistance rating at least equal to that of the floor-wall assembly. The sealing material shall be capable of preventing passage of flame and hot gases sufficient to ignite cotton waste when tested in accordance with ASTM E119.

3.1.9.2 Exterior walls

Permitted unprotected openings in the exterior wall in two consecutive floors lying within

1.5m laterally or vertically shall be separated with flame barriers as similar as sunshades or cornices or projected wall at least 750 mm from the external face of the exterior wall. The flame barrier shall have a fire resistance rating of not less than three-fourths hour.

3.1.10 Exceptions to Fire Resistance Requirements

The provisions of this Section are exceptions to the occupation separation requirements of Table 3.2.1.

3.1.10.1 Fixed partitions

(a)Stores and Offices: In such cases where offices, stores and similar places occupied by one tenant are separated by non-load bearing walls that do not form a corridor serving an occupant load, the partition walls may be constructed of any one of the following:

(i)Noncombustible materials;

(ii)Fire retardant treated wood;

(iii)One hour fire resistive construction;

(iv)Wood panels or similar light construction up to three fourths the height of the room in which placed; and

(v)Wood panels or similar light construction more than three-fourths the height of the room in which placed with not less than upper one fourth of the partition constructed of glass.

(b)Hotels and Apartments: In such cases where non-load bearing walls act as interior partitions in individual dwelling units in apartment houses and guest rooms or suites in hotels when such dwelling units, guest rooms or suites are separated from each other and from corridors by not less than one-hour fire-resistive construction, the partition walls may be constructed of any one of the following:

(i)Noncombustible materials of fire retardant treated wood in buildings of any type of construction; or

(ii)Combustible framing with noncombustible materials applied to the framing in buildings of Type II construction.

(c)Folding, Portable or Movable Partitions: Folding, portable or movable partitions need not have a fire resistance rating if the following conditions are satisfied:

(i)Required exits are not blocked without providing alternative conforming exits;

(ii)Tracks, guides or other approved methods are used to restrict their locations; and

(iii)Flammability shall be limited to materials having a flame-spread classification as set forth in Table 3.3.2 for rooms or areas.

Table 3.3.2: Flame Spread Classification

Table 3.3.2: Flame Spread Classification

(d)Walls Fronting on Streets or Yards: For walls fronting on a street or yard having a width of at least 12 m, certain elements of the wall may be constructed as follows regardless of their fire-resistive requirements:

(i)Bulkheads below show windows, show window frames, aprons and show-cases may be of combustible materials provided the height of such construction does not exceed 5 m above grade.

(ii)Wood veneer of boards not less than 25 mm in nominal thickness or exterior type panels not less than 10 mm in nominal thickness may be used in walls provided:

•the veneer does not extend beyond 5 m above grade; and

•The veneer is placed either directly against noncombustible surface or furred out from such surfaces not to exceed 40 mm with all concealed spaces fire blocked.

(e)Trim: Wood may be used to construct trim, picture moulds, chair rails, baseboards, handrails and show window backing. If there is no requirement for using fire protected construction, unprotected wood doors and windows may be used.

(f)Loading Platform: Noncombustible construction of heavy timber may be used for exterior loading platforms with wood floors not less than 50 mm in nominal thickness. Such wood construction shall not be carried through the exterior walls.

(g)Insulating Boards: Combustible finished boards may be used under finished flooring.

3.1.11 Shaft Enclosures

3.1.11.1 General

Construction requirement for shafts through floors shall conform to the provisions of Tables 3.3.1 (a) and (b).

3.1.11.2 Extent of enclosures

Shaft enclosures shall extend from the lowest floor opening through successive floor openings and shall be enclosed at the top and bottom.

Exceptions:

(a)Shafts need not be enclosed at the top if it extends through or to the underside of the roof sheathing, deck or slab.

(b)Noncombustible ducts carrying vapours, dusts or combustion products may penetrate the enclosure at the bottom.

(c)Shafts need not be enclosed at the bottom when protected by fire dampers conforming to "Test Methods for Fire Dampers and Ceiling Dampers", installed at the lowest floor level within the shaft enclosure.

3.1.11.3 Special provision

In groups other than Occupancies C and D, openings which penetrate only one floor and are not connected with any other floor or basement and which are not concealed within building construction assemblies need not be enclosed.

3.1.11.4 Protection of openings

Openings in shaft enclosures shall be protected with a self-closing or an automatic-closing fire assembly having a fire resistance rating of

(a)one hour for one hour fire resistive walls

(b)one and one-half hours for two hour fire resistive walls

3.1.11.5Rubbish and linen chute termination rooms:

Rubbish and linen chute shall terminate in rooms separate from the remaining of the building having the same fire resistance as required for shafts in Table 3.3.1 (a) and (b) but not less than one hour.

3.1.12 Expansion and Contraction Joints

Expansion and contraction joints provided to accommodate expansion, contraction, wind or seismic movement shall be protected with an approved material having the same degree of fire resistance as that of the wall or floor in which it is installed.

3.1.13 Weather Protection

3.1.13.1 Weather resistive barrier

All weather exposed surfaces shall have a weather barrier to protect the interior wall from damping. Such weather barriers shall have a fire resistance rating of at least equal to that of the wall or floor on which it is applied. Weather resistive barrier need not be used in the following cases:

(i)When exterior covering is of approved waterproof panels

(ii)In back plastered construction

(iii)When there is no human occupancy

(iv)Over water repellent panel sheathing

(v)Under approved paper backed metal or wire fabric lath

(vi)Behind lath and Portland cement plaster applied to the underside of roof and eave projections

3.1.13.2 Flashing and counter flashing

Exterior openings exposed to the weather shall be flashed to make them weather proof. There shall be copings with all parapets. Corrosion resistant metals shall be used for flashing, counter flashing and coping.

3.1.13.3 Waterproofing weather-exposed areas

Waterproofing shall be applied to exposed surfaces like balconies, external stairways and landings.

3.1.13.4 Damp-proofing foundation walls

Outside of foundation walls enclosing a basement floor below finished grade shall be damp-proofed from outside.

3.1.14 Members Carrying Walls

All members carrying masonry or concrete walls shall be fire protected as specified in Table 3.3.1 (a) and (b).

3.1.15 Parapets

Parapets constructed on exterior wall of a building shall have the same degree of fire resistance required for the wall upon which they are erected and there shall be noncombustible faces on the side adjacent to the roof surface for the uppermost 405 mm including counter flashing and coping materials. The height of the parapet shall be at least 750 mm from the upper surface of the roof.

3.1.16 Projections

Sunshades, cornices, projected balconies and overhanging beyond walls of Type I construction shall be of noncombustible materials. Projections from walls of Type II may be of combustible or noncombustible materials.

3.1.17 Guards and Stoppers

3.1.17.1 Guards

Guards or Guardrails shall be provided to protect edges of floor, roof, roof openings, stairways, landings and ramps, balconies or terraces and certain wall, which are elevated more than 750 mm above the grade and as per provisions of this Code.

3.1.17.2 Stoppers

Stopper shall be provided in open parking garages located more than 450 mm above the adjacent grade or back to back parking stall. The height of the stopper shall be at least 300 mm and it shall be positioned at outer edges of a car parking stall.

3.1.18 Insulation

The provisions of this Section are applicable to thermal and acoustical insulations located on or within floor-ceiling and roof ceiling assemblies, crawl spaces, walls, partitions and insulation on pipes and tubing.

Materials used for such insulation and covering shall have a flame spread rating not more than 25 and a smoke density not more than 450.

3.1.19 Atrium

3.1.19.1 General

Atrium may be provided in all groups other than Occupancy J (Hazardous Buildings). Such atrium shall have a minimum opening and are as specified in Table 3.3.3. A vertical opening serving as other than an exit enclosure connecting only two adjacent stories shall be permitted to be open to one of the two stories.

Table 3.3.3: Atrium Opening and Area

Table 3.3.3: Atrium Opening and Area

3.1.19.2 Smoke control system

A mechanically operated air-handling system shall be installed to exhaust the smoke either entering or developed within the atrium.

(a)Exhaust Openings: The location of the exhaust openings shall be in the ceiling or in a smoke trap area immediately adjacent to the ceiling of the atrium above the top of the highest portion of door openings into the atrium.

(b)Supply Openings: Supply openings designed for a minimum of 50 percent of the exhaust volume shall be located at the lowest level of the atrium. Supply air may be introduced by gravity provided the height of the atrium is not more than 18 m and smoke control is established. For atria having height greater than 18 m, supply air shall be introduced mechanically from the floor of the atrium and directed vertically toward the exhaust outlets. Supplemental air supply may be introduced at upper levels in atrium over six storeys in height or when tenant spaces above the second storey are open to the atrium.

(c)Automatic Operation: The smoke control system for the atrium shall be activated automatically by the automatic sprinkler system or smoke detectors installed within the atrium or areas open to the atrium.

(d)Manual Operation: The smoke control system shall also be manually operable for use by the fire department. The smoke control system may be separate from or integrated with other air handling systems. Air handling systems interfering with the smoke control system shall be shut down automatically when the smoke control system is activated.

(e)Smoke Detector Location: Smoke detectors which will automatically operate the smoke control system of the atrium shall be accessible for maintenance, testing and servicing. Their locations shall be as follows:

(i)At the atrium ceiling, spaced in accordance with the manufacturer's instructions.

(ii)On the underside of projections into the atrium, in accordance with the manufacturer's instructions.

(iii)Around the perimeter of the atrium opening on all floors open to the atrium. These detectors shall be spaced no more than 9 m on centre and shall be located within 5 m of the atrium opening.

(iv)If projected beam type smoke detectors are used, they shall be installed in accordance with manufacturer's instructions.

(f)Enclosure of Atrium: Atria shall be separated from the adjacent spaces with fire resistive separation of at least one hour.

Fire windows may be provided in fixed glazed openings when the window has a fire resistive rating of at least three-fourths hour and the area of the opening does not exceed 25 percent of the wall common to the atrium and the room into which the opening is provided.

3.1.20 Mezzanine Floors

Construction of a mezzanine floor shall conform to the requirements of the main floor in which it is constructed but the fire resistance rating need not exceed one hour for unenclosed mezzanines.

Build Struct : Exploring Insights of Civil Engineering